Analog_input objects – Veris Industries E51H5 Install User Manual

Page 25

background image

ZL0109-0C

Page 25 of 32

©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

Installation Guide

Power Monitoring

E51H2, E51H5

TM

#

Object

Name

Description

R/W

NV

Units

Range

Additional Information

AI1

KWh_Net

Accumulated Real

Energy: Net (Import -

Export)

R

NV

kWh

-3.4+E38 - 3.4+E38

AI2

KWh_Import

Real Energy Import

R

NV

kWh

0 - 3.4+E38

AI3

KWh_Export

Real Energy Export

R

NV

kWh

0 - 3.4+E38

AI4

KVARh_Q1

Reactive Energy

Quadrant 1

R

NV

kVARh 0 - 3.4+E38

The Units property of object AI4 reports that these units are kWh because there

is no unit type in the BACnet standard for KVARh

AI5

KVARh_Q2

Reactive Energy

Quadrant 2

R

NV

kVARh 0 - 3.4+E38

The Units property of object AI5 reports that these units are kWh because there

is no unit type in the BACnet standard for kVARh

AI6

KVARh_Q3

Reactive Energy

Quadrant 3

R

NV

kVARh 0 - 3.4+E38

The Units property of object AI6 reports that these units are kWh because there

is no unit type in the BACnet standard for kVARh

AI7

KVARh_Q4

Reactive Energy

Quadrant 4

R

NV

kVARh 0 - 3.4+E38

The Units property of object AI7 reports that these units are kWh because there

is no unit type in the BACnet standard for kVAh

AI8

Net_KVAh

Apparent Energy: Net

(Import - Export)

R

NV

kVAh

-3.4+E38 - 3.4+E38

The Units property of object AI8 reports that these units are kWh because there

is no unit type in the BACnet standard for kVAh

AI9

KVAh_Import

Apparent Energy

Import

R

NV

kVAh

0 - 3.4+E38

The Units property of object AI9 reports that these units are kWh because there

is no unit type in the BACnet standard for kVAh

AI10

KVAh_Export

Apparent Energy

Export

R

NV

kVAh

0 - 3.4+E38

The Units property of object AI10 reports that these units are kWh because there

is no unit type in the BACnet standard for kVAh

AI11

KW_Total

Total Instantaneous

Real Power

R

kW

0 - Max_Power (AI76)

AI12

KVAR_Total

Total Instantaneous

Reactive Power

R

kVAR

0 - Max_Power (AI76)

AI13

KVA_Total

Total Instantaneous

Apparent Power

R

kVA

0 - Max_Power (AI76)

AI14

PF_Total

Total Power Factor

R

-1.00 - 1.00

AI15

Volts_LL_Avg Voltage, L-L, Average

of Active Phases

R

Volts

AI16

Volts_LN_Avg Voltage, L-N, Average

of Active Phases

R

Volts

AI17

Current

Average

Current, Average of

Active Phases

R

Amps

AI18

Frequency

Frequency

R

Hz

45.0 - 65.0

Returns QNAN if frequency is out of range (or no voltage input present on Phase

A)

Analog_Input
Objects

Use the Present_Value property of the Analog_Input objects for all read-only numeric variables in the meter other than those
used specifically for device configuration (in the Device Object) or data logging (in the Trend_Log objects). Only the E51H5
supports the data logging capability.

These objects support the Description and Reliability object properties and all required Analog_Input object properties. None
of them are writable. The values that are not instantaneous (i.e., Accumulated Energy, Max Demand, Pulse Input Counts) are
non-volatile. They are not updated while control power is inactive, but their past values are retained when power is restored. The
Present_Value of the accumulated data objects (AI1-AI10 and AI31-AI54) use floating-point data types (all AI objects use floating
point data points). The resolution of the accumulated values decreases as the value grows larger over time and more of the
significant digits precede the decimal point. If the size of the value limits the resolution unacceptably, read and store the current
value offline and reset the accumulators to restore finer resolution.

For complete assurance, check the Reliabilty property for a No_Fault_Detected status before reading the Present_Value. If the
line voltage or input frequency of the system being monitored falls out of the supported range, the corresponding alert bits
(BI1-BI7) are set and the reliability property of any values that cannot be accurately measured under those conditions returns
Unreliable_Other.