10

Config.

parameters

Significance

Default value

Adjustments

Get From

Get From Reference

address

Default value=255

Conditional parameter to Wireless models (VH72xxX1000W)

This parameter / function is not currently supported by the wireless humidistat

BI 1

Binary input no.1
configuration
Default value = None

None, No function will be associated with the input
Canister, a back-lit flashing Canister alarm will be displayed on the humidistat
LCD screen when the input is energized
Service, a back-lit flashing Service alarm will be displayed on the humidistat
LCD screen when the input is energized

• Open contact input = function not energized
• Closed contact input = function energized

Lockout

Keypad lockout levels
Default value = 0 No lock

0 = No lock
1 = Low level lock

Level

Sys

Mode

Setpoints

0

Yes access

Yes access

1

No access

No Access

SeqOpera

Sequence of operation

Default value is = 2

2 position On-Off

dehumid

Sets the desired control operation of the humidistat

Available sequence of operation is dependent on humidistat model


0 = Ahu - 0-10V Analog humidification only

1 = 2Phu - 2 position On-Off humidification

2 = 2Pdh - 2 position On-Off dehumid only

3 = Ahu 2Pdh - Analog humidification & 2 position On-Off dehumidification

4 = 2Phu2Pdh - On-Off humidification & 2 position On-Off dehumidification

Units

Sets the display scale of
the thermostat
Default value = °F

°F for Fahrenheit scale
°C for Celsius scale

Humi max

Maximum humidify set

point limit

Default value = 90 %

Maximum humidity set point adjustment. Humidity set point range is:

10% to 90 %

Dehu min

Minimum dehumidify set

point limit

Default value = 15%

Minimum Dehumidification set point adjustment. Cooling setpoint range is:

15% to 95%

MenuScro

Menu Scroll

Default value = On

This parameter allow the user to select from scrolling system mode, room
humidity level. Disabling the scrolling function will render the display with the
Room humidity only.

Hum cph

On/Off humidification

devices cycles per hour

setting:

Default value = 4 C.P.H.

Will set the maximum number cycles per hour under normal control operation

for the relay humidification output. It represents the maximum number of cycles

that the equipment will turn ON and OFF in one hour.

Note that a higher C.P.H will represent a higher accuracy of control at the

expense of wearing mechanical components faster. 3, 4, 5, 6,7 & 8 C.P.H.

Dhu cph

On/Off dehumidification

devices cycles per hour

setting:

Default value = 4 C.P.H.

Will set the maximum number cycles per hour under normal control operation

for the relay dehumidification output. It represents the maximum number of

cycles that the equipment will turn ON and OFF in one hour.

Note that a higher C.P.H will represent a higher accuracy of control at the

expense of wearing mechanical components faster. 3, 4, 5, 6,7 & 8 C.P.H.

hum lock

Humidification outside air

temperature lockout

Default value = 120 °F ( 49

°C )

Disables Humidification operation based on outdoor air humidity.

Function will only be enabled if OS (outside air humidity sensor) is connected.

From -15 °F up to 120 °F ( -26 °C up to 49 °C )