Installation Guide

Power Monitoring

E51C2A, E51C3A

TM

E51C2A FDS

E51C3A L

og

Regist

er

R/W NV Format Units Scale

Range

Description

• 287/288 R

Float

Volt

Voltage, L-N (V), average of active phases

• 289/290 R

Float

Amp

Current, average of active phases

• 291/292 R

Float

Hz

45.0-65.0

Frequency

• 293/294 R

Float

kW

Total Real Power Present Demand

• 295/296 R

Float

kVAR

Total Reactive Power Present Demand

• 297/298 R

Float

kVA

Total Apparent Power Present Demand

• 299/300 R

NV Float

kW

Total Real Power Max. Demand

Import

• 301/302 R

NV Float

kVAR

Total Reactive Power Max. Demand

• 303/304 R

NV Float

kVA

Total Apparent Power Max. Demand

• 305/306 R

NV Float

kW

Total Real Power Max. Demand

Export

• 307/308 R

NV Float

kVAR

Total Reactive Power Max. Demand

• 309/310 R

NV Float

kVA

Total Apparent Power Max. Demand

• 311/312 R

Float

Reserved, reports QNAN (0x7FC00000)

• 313/314 R

Float

1

0-4294967040

Pulse Counter 1 (Import Real Energy)

Contact closure counters. Valid for both pulse

inputs and outputs. E51CxA counts are shown

in (). See register 144 for the weight of each

pulse output count. These values are derived

from the 32 bit integer counter and roll over

to 0 when the integer counters do. Inputs are

user defined.

• 315/316 R

Float

1

0-4294967040

Pulse Counter 2 (Export Reactive Energy

Floating Point Data: Per Phase

• 317/318 R

Float

kWh

Accumulated Real Energy, Phase A

Import

Accumulated Real Energy (Ph)

• 319/320 R

Float

kWh

Accumulated Real Energy, Phase B

• 321/322 R

Float

kWh

Accumulated Real Energy, Phase C

• 323/324 R

Float

kWh

Accumulated Real Energy, Phase A

Export

• 325/326 R

Float

kWh

Accumulated Real Energy, Phase B

• 327/328 R

Float

kWh

Accumulated Real Energy, Phase C

• 329/330 R

Float

kVARh

Accumulated Q1 Reactive Energy, Phase A

Quadrant 1

Import

Accumulated

Reactive Energy

(Qh)

• 331/332 R

Float

kVARh

Accumulated Q1 Reactive Energy, Phase B

• 333/334 R

Float

kVARh

Accumulated Q1 Reactive Energy, Phase C

• 335/336 R

Float

kVARh

Accumulated Q2 Reactive Energy, Phase A

Quadrant 2

• 337/338 R

Float

kVARh

Accumulated Q2 Reactive Energy, Phase B

• 339/340 R

Float

kVARh

Accumulated Q2 Reactive Energy, Phase C

• 341/342 R

Float

kVARh

Accumulated Q3 Reactive Energy, Phase A

Quadrant 3

Export

• 343/344 R

Float

kVARh

Accumulated Q3 Reactive Energy, Phase B

• 345/346 R

Float

kVARh

Accumulated Q3 Reactive Energy, Phase C

• 347/348 R

Float

kVARh

Accumulated Q4 Reactive Energy, Phase A

Quadrant 4

• 349/350 R

Float

kVARh

Accumulated Q4 Reactive Energy, Phase B

• 351/352 R

Float

kVARh

Accumulated Q4 Reactive Energy, Phase C

• 353/354 R

Float

kVAh

Accumulated Apparent Energy, Phase A

Import

Accumulated Apparent Energy (Sh)

• 355/356 R

Float

kVAh

Accumulated Apparent Energy, Phase B

• 357/358 R

Float

kVAh

Accumulated Apparent Energy, Phase C

• 359/360 R

Float

kVAh

Accumulated Apparent Energy, Phase A

Export

• 361/362 R

Float

kVAh

Accumulated Apparent Energy, Phase B

• 363/364 R

Float

kVAh

Accumulated Apparent Energy, Phase C

Modbus Point Map (cont.)