beautypg.com

Standard modbus default settings, Modbus point map overview (cont.) – Veris Industries E51C3A Install User Manual

Page 19

background image

ZL0122-0A

Page 19 of 34

©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 09132

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

Installation Guide

Power Monitoring

E51C2A, E51C3A

TM

R/W

R=read only
R/W=read from either int or float formats, write only to integer format.

NV

Value is stored in non-volatile memory. The value will still be available if the meter experiences a power loss and reset.

Format

UInt

Unsigned 16-bit integer.

SInt

Signed 16-bit integer.

ULong

Unsigned 32-bit integer; Upper 16-bits (MSR) in lowest-numbered / first listed register (001/002 = MSR/LSR).

SLong

Signed 32-bit integer; Upper 16-bits (MSR) in lowest-numbered / first listed register (001/002 = MSR/LSR).

Float

32-bit floating point; Upper 16-bits (MSR) in lowest-numbered / first listed register (257/258 = MSR/LSR). Encoding is

per IEEE standard 754 single precision.

Units

Lists the physical units that a register holds.

Scale

Factor

Some Integer values must be multiplied by a constant scale factor (typically a fraction), to be read correctly. This is done to allow

integer numbers to represent fractional numbers.

Range

Defines the limit of the values that a register can contain.

Standard Modbus
Default Settings

Setting

Value

Modbus

Register

Setup Password

00000

Reset Password

00000

System Type

40 (3 + N) Wye

130

CT Primary Ratio (if CTs are not included)

100A

131

CT Secondary Ratio

QNAN

132

PT Ratio

1:1 (none)

133

System Voltage

600 V L-L

134

Max. Theoretical Power
(Analog Output: full scale (20mA or 5V))

104 kW

135

Display Mode

1 (IEEE units)

137

Phase Loss

10% of System Voltage (60V), 25% Phase to Phase Imbalance

142, 143

Pulse Energy

1 (kWh/pulse)

144

Demand: number of sub-intervals per interval

1 (block mode)

149

Demand: sub-interval length

900 sec (15 min)

150

Modbus Address

001

Modbus Baud Rate

19200 baud

Modbus Parity

None

Log Read Page

0

158

Logging Configuration Register

0

159

Log Register Pointer 1

3 (Import Real Energy MSR)

169

Log Register Pointer 2

4 (Import Real Energy LSR)

170

Log Register Pointer 3

5 (Export Real Energy MSR)

171

Log Register Pointer 4

6 (Export Real Energy LSR)

172

Log Register Pointer 5

29 (Real Demand)

173

Log Register Pointer 6

30 (Reactive Demand)

174

Log Register Pointer 7

31 (Apparent Demand)

175

Log Register Pointer 8

155 (Month/Day)

176

Log Register Pointer 9

156 (Year/Hour)

177

Log Register Pointer 10

157 (Minutes/Seconds)

178

Modbus Point Map
Overview (cont.)