R/W NV Format Units Scale

Range

Description

• 147

R

NV UInt

0-32767

Count of Energy Accumulator resets

• 148

R

UInt

Reserved (returns 0)

• 149

R/W NV UInt

1-6

Number of Sub-Intervals per Demand Interval. Sets the number of sub-intervals that

make a single demand interval. For block demand, set this to 1. Default is 1. When Sub-

Interval Length register #150 is set to 0 (sync-to-comms mode), this register is ignored. Demand

Calculation

• 150

R/W NV UInt

Seconds

0, 10-32767

Sub-Interval Length in seconds. For sync-to-comms, set this to 0 and use the reset

register (129) to externally re-start the sub-interval. On the E51C3A, this is also the

logging interval.

• 151

R/W

UInt

1-32767

Reserved (returns 0)

• 152

R

NV UInt

0-32767

Power Up Counter.

• 153

R

NV UInt

0-32767

Output Configuration. E51CxA units have a N.O. energy contact and N.C. (Normally Closed - Form B) Phase

Loss contact, so this register always returns 0.

• 154

R

UInt

Reserved, returns 0

Logging Configuration and Status

• 155

R/W NV UInt

Day /

Month

See Bytes

Most Significant Byte (MSB) Least Significant Byte (LSB)

Date / Time Clock. Following a power cycle,

resets to:

Day 01 Month 01
Hour 00 Year (20) 00

Day 1-31 (0x01-0x1F)

Month 1-12 (0x01-0x0C)

• 156

R/W NV UInt

Hour /

Year

See Bytes

Hour 0-23 (0x00-0x17)

Year 0-199 (0x00-0xC7)

• 157

R/W NV UInt

Seconds

/

Minutes

See Bytes

Seconds 0-59 (0x00-0x3B)

Minutes 0-59 (0x00-0x3B)

• 158

R/W NV UInt

0-10

Logging Read Page Register. Selects which of the Register Logs to read (see registers 169-178). 1-10 are valid

entries that put the meter into log reading mode, temporarily pausing logging. When set to 0 (no variable

selected for reading), normal logging resumes. The meter buffers one set of log entries while in reading

mode if a sub-interval timeout occurs (read/write collision). Default is 0.

Warning: this buffered data is written to the log, and logging resumes on the following sub-interval timeout

whether the page register has been cleared or not, resulting in the appearance of data moving in the buffer

during reads. To avoid this, complete log buffer reads and this register set back to 0 in less time than the

Demand Sub-interval (preferred) or halt logging by setting Bit 1 in register 158 (logs may be missed)

• 159

R/W NV UInt

Logging Configuration Register (Bit Mapped):
Bit 0: Clear to 0 for Circular log buffer mode. Set to 1 for single shot logging mode. Default is 0 (Circular).
Bit 1: Clear to 0 to enable Logging. Set to 1 to halt logging. Default is 0 (Log).

Modbus Point Map (cont.)