Installation Guide

Power Monitoring

E51C2A, E51C3A

TM

Next

Set Passwords:

SETUP - The Password to enter the SETUP menu.

RESET - The Password to enter the RESET menu.

RESET

--------

00000

SPASS

Setup

Passwords

SETUP

--------

00000

Back

Next

SDMND

INTRV

--------

6

5

4

3

2

1

Demand

SEC

--------

00900

Back

Set Demand Interval:

INTRV - The number of Sub-Intervals (1 to 6) in a Demand Interval.

Default is 1 (block demand).

SEC - Sub-Interval length in seconds. Default is 900 (15 minutes).

Set to 0 for external sync-to-comms (Modbus units only).

Next

S DIS

Display

Units

UNITS

--------

IEEE

IEC

Back

Set Display Units: +/- to switch between:

IEEE – VLL VLN W VAR VA Units.

IEC - U V P Q S Units.

To Setup p. 1 “S PWR”

Max

PPS

--------

1

2

5

10

20

50

Pulse

Output

Next

Set Pulse:

The System Type , CT size, PT Ratio, and System Voltage must

all be configured before setting the Pulse Energy. If any of these

parameters are changed, the meter will hunt for a new Pulse

Duration, but will not change the Pulse Energy. If it cannot find a

solution, the meter will display the wrench, show “ConF” in the

ALARM -> PULSE screen, and enable Energy pulse output

configuration error bit in the Modbus Diagnostic Alert Bitmap (if

equipped).

Wh/P - Set Pulse Energy: In Watt Hours (& VAR Hours, if

present) per Pulse. When moving down to a smaller energy, the

meter will not allow the selection if it cannot find a pulse duration

that will allow the pulse output to keep up with Theoretical

Maximum System Power (see S_PWR screen). When moving

up to a larger energy, the meter will jump to the first value where

it can find a valid solution.

mS/P – Minimum Pulse Duration Time: This read only value

is set by the meter to the slowest duration (in mS per closure)

that will keep up with the Theoretical Maximum System Power.

The open time is greater than or equal to the closure time. The

maximum Pulses Per Second (PPS) is shown in yellow.

mS/P

--------

500

250

100

50

25

10

SPULS

Back

Wh/P

--------

10000

1000

100

10

SPLOS

Back

IMBAL

--------

0.25

Next

VOLTS

--------

0.10

Set Phase Loss:

VOLTS - Phase Loss Voltage: The fraction of the system

voltage below which Phase Loss Alarm is on. For system

types with neutral, the Line to Neutral voltage is also

calculated and tested. If the System Voltage is 600 and the

fraction is set to 0.10, then the Phase Loss threshold will be

60 volts.

IMBAL - Phase Loss Imbalance: The fractional difference

in Line to Line voltages above which Phase Loss Alarm is

on. For system types with neutral, the Line to Neutral

voltages are also tested. For system types 1+N (10) and 2

(11) , imbalance is not tested.

Phase

Loss

Back

To

SETU

P

To Setup page 1 “S COM”

UI for Setup