Installation guide, Troubleshooting – Veris Industries H8026 Install User Manual
Page 9
H8025/8026
Z201640-0H
PAGE 9
©2010 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
11101
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
INSTALLATION GUIDE
TROUBLESHOOTING
Problem
Solution
Status LED does not blink
Check fuses and voltage connections. Status LED should
blink regardless of CTs, N2 BUS connections, and DIP
switch setting.
Power meter interferes with
another device on the N2 BUS
Set DIP switches to a different N2 address not in use.
Readings seem highly inaccurate. • Check that each CT is installed on the conductor with
the corresponding color voltage input lead attached. In
most cases, incorrect wiring will cause the STATUS LED
to blink RED (slowly). However, a power factor lower
than 0.5 could cause the LED to blink this way, even if
the unit is installed properly.
• It does not matter which side of the CT faces towards
the load.
• If current is below 7% of full scale maximum for the
CT, use a smaller CT or wrap each wire through the CT
multiple times
•Check current with an amp-clamp.
Expected power:
kW = Volts x Amps x 1.732 x PF / 1000
kW = Horsepower x 0.746
PF is usually 0.7 to 0.95, depending on the load.
Meter goes offline when load is
switched off.
Voltage leads must be connected on the Line side of the
conductor. The power meter cannot communicate on
the N2 BUS without voltage.
Status LED blinks red.
• If the LED blinks quickly (i.e., about 5 blinks in two
seconds), then the CT rating is too low.
• If the LED blinks slowly (i.e., about 1 blink in two
seconds) the CTs are not installed on the correct
conductors, or the power factor is less than 0.5. The
meter can accurately measure these low PFs, but few
loads operate normally at such a low power factor.