beautypg.com

Installation guide, Address selection switches – Veris Industries H8026 Install User Manual

Page 4

background image

H8025/8026

Z201640-0H

PAGE 4

©2010 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

11101

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

TM

INSTALLATION GUIDE

ADDRESS SELECTION SWITCHES

Each device on the N2 BUS must have a unique address. These switches must be set to assign a unique address before the device is connected to the N2 BUS. If an address is
selected which conflicts with another device on the N2 BUS, both devices will be unable to communicate.

When setting the N2 BUS address, choose an address number which is not in use. Only N2 addresses in the range of 1 to 63 may be used. Set the switches for the selected
address by following the diagram below. This address will be required when adding the meter to Metasys®.