Installation guide – Veris Industries H8026 Install User Manual
Page 6
H8025/8026
Z201640-0H
PAGE 6
©2010 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
11101
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
INSTALLATION GUIDE
POINT MAP FOR H8026 (ENHANCED DATA STREAM), N2 PROTOCOL
NPT
NPA
UNITS
POINT DESCRIPTION
RANGE/VALUE
NOTES
BI
1
kWh, kW*
Consumption (accumulation)
100A: 0.0025 kWh/count
300A: 0.01 kWh/count
400A: 0.01 kWh/count
800A: 0.02 kWh/count
1600A: 0.04 kWh/count
2400A: 0.08 kWh/count
Intended for use as an accumulator (ACM) type. It should not be read as a binary status.
AI
1
kWh
Consumption
100A: 0 to 10737418.24
2400A: 0 to 343597383.7
Allows direct view of kWh accumulator as an AI point. For large values, BI-1 is more precise.
AI
2
kW
Real Power
100A: 0 to 83.1
2400A: 0 to 1995.3
AI
3
kVAR
Reactive Power
100A: 0 to 83.1
2400A: 0 to 1995.3
AI
4
kVA
VA (apparent power)
100A: 0 to 83.1
2400A: 0 to 1995.3
AI
5
Power Factor, total
0 to 1.0
Reads the effective power factor for all phases (not an average of AI-15, AI-16, and AI-17).
AI
6
kW
Average Real Power
100A: 0 to 83.1
2400A: 0 to 1995.3
Reads the average real power (kW). This is intended for demand window applications, where
this point is read at the end of each window and then reset via BO-2.
AI
7
kW
Mimimum Real Power
100A: 0 to 83.1
2400A: 0 to 1995.3
Reads the min. real power since it was reset via BO-2. Real power is internally monitored in
200msec intervals.
AI
8
kW
Maximum Real Power
100A: 0 to 83.1
2400A: 0 to 1995.3
Reads the max. (peak) real power since it was reset via BO-2. Peak power is internally
monitored in 200msec intervals.
AI
9
Volts
Voltage, Line-to-Line
0 to 480
Reads the average line to line voltages.
AI
10
Volts
Voltage, Line-to-Neutral
0 to 277
Reads the average line to neutral voltages.
AI
11
Amps
Current
100A: 0 to 100
2400A: 0 to 2400
Reads the current.
AI
12
kW
Real Power, ØA
100A: 0 to 27.7
2400A: 664.8
AI
13
kW
Real Power, ØB
100A: 0 to 27.7
2400A: 664.8
AI
14
kW
Real Power, ØB
100A: 0 to 27.7
2400A: 664.8
AI
15
Power Factor, ØA
0 to 1.0
AI
16
Power Factor, ØB
0 to 1.0
AI
17
Power Factor, ØC
0 to 1.0
AI
18
Volts
Voltage, ØA to ØB
190 to 480
The meter is powered by A-B voltage; it will not operate at low voltage.
AI
19
Volts
Voltage, ØB to ØC
0 to 480
AI
20
Volts
Voltage, ØA to ØC
0 to 480
AI
21
Volts
Voltage, ØA to Neutral
0 to 277
AI
22
Volts
Voltage, ØB to Neutral
0 to 277
AI
23
Volts
Voltage, ØC to Neutral
0 to 277
AI
24
Amps
Current, ØA
100A: 0 to 100
2400A: 0 to 2400
AI
25
Amps
Current, ØB
100A: 0 to 100
2400A: 0 to 2400
AI
26
Amps
Current, ØC
100A: 0 to 100
2400A: 0 to 2400
ADI
1
Amps
Preset kWh, LSW
-32768 to 32767
Allows the lower 16 bits of the kWh accumulator to be preset
ADI
2
Preset kWh, MSW
-32768 to 32767
Allows the upper 16 bits of the kWh accumulator to be preset
BO
1
Reset kWh
0 = NA
1 = Reset kWh
Resets the kWh accumulator to zero. The value will return to "off." **
BO
2
Reset Min/Max/Avg
0 = NA
1 = Reset min/max/avg
Command to "on" to reset the AI-5, AI-6, and AI-7. THe value will return to "off." **