Installation guide – Veris Industries H8026 Install User Manual
Page 5
H8025/8026
Z201640-0H
PAGE 5
©2010 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
11101
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
INSTALLATION GUIDE
POINT MAP FOR H8025, N2 PROTOCOL
NPT
NPA
UNITS
POINT DESCRIPTION
RANGE/VALUE
NOTES
BI
1
kWh, kW*
Consumption (accumulation)
100A: 0.0025 kWh/count
300A: 0.01 kWh/count
400A: 0.01 kWh/count
800A: 0.02 kWh/count
1600A: 0.04 kWh/count
2400A: 0.08 kWh/count
Intended for use as an accumulator (ACM) type. It should not be
read as a binary status.
AI
1
kWh
Consumption
100A: 0 to 10737418.24
2400A: 0 to 343597383.7
Allows direct view of kWh accumulator as an AI point. For large
values, BI-1 is more precise.
AI
2
kW
Real Power
100A: 0 to 83.1
2400A: 0 to 1995.3
BO
1
Reset kWh
0 = NA
1 = Reset kWh
Resets the kWh accumulator to zero. The value will return to
"off." **
ADI
1
Preset kWh, LSW
-32768 to 32767
Allows the lower 16 bits of the kWh accumulator to be preset
ADI
2
Preset kWh, MSW
-32768 to 32767
Allows the upper 16 bits of the kWh accumulator to be preset
* kWh when displayed in “analog consumption units,” kW when displayed in “analog units.”
** Do not define BO-1 as auto-restorable. If they are defined in a Metasys CS object or in Companion, they should be commanded to Ø after commanding to 1 to avoin
unintentional reset.
Only BO-1, BO-2, ADI-1, and ADI-2 are capable of being commanded or overridden.
Phase A corresponds to the red lead, Phase B to the black lead, and Phase C to the yellow.