TM

Problem

Cause

Solution

The maintenance wrench icon appears

in the power meter display.

There is a problem with the inputs

to the power meter.

See the Alert sub-menu or the Diagnostic Alert Modbus

Register 146

The display is blank after applying

control power to the meter.

The meter is not receiving adequate

power.

Verify that the meter control power are receiving the required

voltage.

Verify that the heart icon is blinking.
Check the fuse.

The data displayed is inaccurate.

Incorrect setup values

Verify the values entered for power meter setup parameters

(CT and PT ratings, system type, etc.). See the Setup section.

Incorrect voltage inputs

Check power meter voltage input terminals to verify

adequate voltage.

Power meter is wired improperly.

Check all CTs and PTs to verify correct connection to the same

service, PT polarity, and adequate powering. See the Wiring

Diagrams section for more information.

Cannot communicate with power meter

from a remote personal computer.

Power meter address is incorrect.

Verify that the meter is correctly addressed (see Setup

section).

Power meter baud rate is incorrect.

Verify that the baud rate of the meter matches that of

all other devices on its communications link (see Setup

section).

Communications lines are

improperly connected.

Verify the power meter communications connections (see the

Communications section).

Verify the terminating resistors are properly installed on

both ends of a chain of units. Units in the middle of a chain

should not have a terminator.

Verify the shield ground is connected between all units.

Troubleshooting

China RoHS Compliance Information
(EFUP Table)

部件名称

产品中有毒有害物质或元素的名称及含量Substances

铅 (Pb) 汞 (Hg)

镉 (Cd)

六价铬 (Cr(VI))

多溴联苯(PBB)

多溴二苯醚(PBDE)

电子线路板

X

O

O

O

O

O

O = 表示该有毒有害物质在该部件所有均质材料中的含量均在 SJ/T11363-2006 标准规定的限量要求以下.

X = 表示该有毒有害物质至少在该部件的某一均质材料中的含量超出SJ/T11363-2006标准规定的限量要求.

Z000057-0A