Modbus point map (cont.) – Veris Industries E50C3A Install User Manual

Page 20

background image

ZL0116-0A

Page 20 of 26

©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 07132

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

Installation Guide

Power Monitoring

E50B1A, E50C2A, E50C3A

TM

E50C2A FDS

E50C3A L

og

E50xxA REG.

R/W NV Format

Units

Scale

Range

Description

• 043*

R

NV ULong

0-0xFFFF

Pulse Counter 1 (Real Energy)

MSR Contact Closure Counters. Valid for

both Pulse inputs and outputs. E50xx

counts are shown in (). See register

144 (Energy per Pulse) for the Wh per

pulse count. Clear via register 129.

Inputs are user defined.

• 044*

LSR

• 045*

R

NV ULong

0-0xFFFF

Pulse Counter 2 (Reactive Energy)

MSR

• 046*

LSR

• 047*

R

NV ULong

kWh

E

0-0xFFFF

Real Energy Consumption
Phase A

MSR

Clear via reset register

• 048*

LSR

• 049*

R

NV ULong

kWh

E

0-0xFFFF

Real Energy Consumption
Phase B

MSR

• 050*

LSR

• 051*

R

NV ULong

kWh

E

0-0xFFFF

Real Energy Consumption
Phase C

MSR

• 052*

LSR

Configuration

• 129

R/W

UInt

N/A

Command Register:
- Write 30078 (0x757E) to clear all Energy Accumulators to 0.
- Write 21211 (0x52DB) to begin new Demand Sub-Interval calculation cycle. Takes effect at the end of the next

1 second calculation cycle. Write no more frequently than every 10 seconds.

- Write 21212 (0x52DC) to reset Max Demand values to Present Demand Values. Takes effect at the end of the

next 1 second calculation cycle. Write no more frequently than every 10 seconds.

- Write 16640 (0x4100) to Reset Logging (E50C3A only).
- Write 16498 (0x4072) to Clear Pulse Counters to 0.
- Read always returns 0.

• 130

R/W NV UInt

10,
11,
12,
31,
40

Single Phase: A + N

System Type
(See Manual. Note: only the indicated

phases are monitored for Phase Loss)

Single Phase: A + B
Single Split Phase: A + B + N
3 phase ∆, A + B + C, no N
3 phase Y, A + B + C + N

• 131

R/W NV UInt

Amps

5-5000

CT Ratio – Primary

Current Inputs

• 132

R

NV UInt

n/a

Reserved, always returns QNAN

• 133

R/W NV UInt

100

0.01-320.00 PT Ratio: The meter scales this value by 100 (i.e. entering 200 yields a potential transformer ratio of 2:1). The

default is 100 (1.00:1), which is with no PT attached. Set this value before setting the system voltage (below)

• 134

R/W NV UInt

82-32000

System Voltage: This voltage is line to line, except for system type 10 which is line to neutral. The meter uses

this value to calculate the full scale power for the analog outputs and pulse configuration (below), and as full

scale for phase loss (register 142). The meter will refuse voltages that are outside the range of 82-660 volts

when divided by the PT Ratio (above).

• 135

R

NV UInt

kW

W

1-32767

Theoretical Maximum System Power: This read-only value is the theoretical max. power the meter can expect to

see on a service. This value is 100% of scale on the analog output (0-5 VDC or 4-20 mA), if equipped. The meter

recalculates this value if the user changes the CT size, system type, or system voltage. This integer value has

the same scale as other integer power registers (see register 140 for power scaling).

• 136

R

UInt

Reserved, always returns 0

• 137

R/W NV UInt

0,1

Display Units: 0 = IEC (U, V, P, Q, S), 1 = IEEE (default: VLL, VLN, W, VAR, VA)

Modbus Point Map (cont.)