beautypg.com

Ui for setup – Veris Industries E50C3A Install User Manual

Page 14

background image

ZL0116-0A

Page 14 of 26

©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 07132

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

Installation Guide

Power Monitoring

E50B1A, E50C2A, E50C3A

TM

UI for Setup

Next

Next

From:

SETUP > PASWD

ADDR

--------

001

BAUD

--------

38400

19200

9600

4800

2400

1200

PAR

--------

nOnE

EvEn

Odd

Set Communications Parameters:

ADDR - Modbus Address: 1 – 247.

+ increments the selected (blinking) digit.

- selects the digit to the left.

BAUD - Baud Rate: 1200 – 38400 Baud

PAR - Parity: Odd, Even, None

+

or

to step through the options.

Set Current Transducer:

CT SZ - CT Size: in Amps. Maximum is 5000 Amps.

Set System Configuration:

SYSTM: + or to step through the following System Type options:

System Reg 130 CTs Description

3L-1n

40

3 Wye Three Phase: A, B, & C with Neutral (Default).

3L

31

3 Delta Three Phase: A, B & C; no Neutral

2L-1n

12

2 Single Split Phase: A & B with Neutral

2L

11

1 Single Phase: A & B; no Neutral

1L-1n

10

1 Single Phase: A to Neutral

System

Type

Current

Transformer

S SYS

Next

S CT

CT SZ

--------

100

SYSTM

--------

3L-1n

3L

2L-1n

2L

1L-1n

Bac

k

To

SETU

P

Back

Back

Back

S COM

To Setup p. 2 “SPLOS”

Next

S PT

Set Potential Transfomer Ratio:

RATIO – Potential transformer step down is RATIO:1. Default is 1:1

(No PT installed). See Install for wiring diagrams. This value must be

set before the System Voltage (if used).

Potential

Transformer

RATIO

--------

001.00

Back

S V

Back

Sytem

Voltage

Next

Set System Voltage:

V LL – The nominal Line to Line Voltage for the system. This is used

by the meter to calculate the theoretical maximum system power, and

as the reference voltage for setting the Phase Loss threshold.

Maximum is 32000 Volts. For system type 1+N (10), this is a Line to

Neutral Voltage, indicated by “V LN”. Note: the meter will reject settings

that are not within the meter’s operating range when divided by the PT

ratio.

V LL

--------

00600

S PWR

Back

Sytem

Voltage

MX KW

--------

103.92

Next

System Power:

MX KW – The theoretical Maximum System Power is calculated by the

meter from the System Voltage, CT size, and System Type. Power

Factor is assumed to be unity. The value of System Power is used to

determine which combinations of pulse weight and duration are valid

and will keep up with the maximum power the meter will see. This value

is read only.

Note:

Bold is the Default.

To Setup p. 2 “SPASS”

RS-485

Output

† When leaving this parameter screen using the right button ( ), the display will
briefly indicate “SAvEd)” to confirm that any changes made have been accepted.