Installation Guide

Power Monitoring

E50B1A, E50C2A, E50C3A

TM

Solid State Output

The E50xxxA have one normally open (N.O.) KY Form A output and one normally closed (N.C.) output.* One is dedicated to energy
(Wh), and the other to Alarm. The E50B1A also provides an additional N.O. reactive energy (VARh) contact. See the Setup section
for configuration information.

~

=

~

=

≤ 100 mA

≤ 100 mA

~

=

≤ 100 mA

Alarm

Energy

Output

+ – S

LOAD

LOAD

LOAD

Power Source

3-30 VDC
6-30 VAC

Power Source

3-30 VDC
6-30 VAC

Over-Current Protective
Device** (not supplied)

Power Source

3-30 VDC
6-30 VAC

E50B1A only

The solid state pulse outputs are rated for 30VAC/DC nom.
Maximum load current is 100mA at 25°C. Derate 0.56mA per °C above 25°C.
* While the relay used for the Phase Loss contact is Normally Closed (contacts are closed when the meter is not powered), closure indicates the presence of an
alarm; either loss of phase, when the meter is powered, or loss of power when the meter is not. The contacts are open when the meter is powered and no phase
loss alarm conditions are present
** The over-current protective device must be rated for the short circuit current at the connection point.

Main Menu

IEC

IEEE

Description

D

D

Demand

MAX

M

Maximum Demand

P

W

Present Real Power

Q

VAR

Present Reactive Power

S

VA

Present Apparent Power

A

A

Amps

UAB, UBC, UAC

VAB, VBC, VAC

Voltage Line to Line

V

VLN

Voltage Line to Neutral

PF

PF

Power Factor

U

VLL

Voltage Line to Line

HZ

HZ

Frequency

KSh

KVAh

Accumulated Apparent

Energy

KQh

KVARh

Accumulated Reactive

Energy

KPh

KWh

Accumulated Real Energy

PLOSS

PLOSS

Phase Loss

LOWPF

LOWPF

Low Power Factor Error

Main Menu

IEC

IEEE

Description

F ERR

F ERR

Frequency Error

I OVR

I OVR

Over Current

V OVR

V OVR

Over Voltage

PULSE

PULSE

kWh Pulse Output Overrun

(configuration error)

_PHASE

_PHASE

Summary Data for 1, 2, or 3

active phases

ALERT

ALERT

Diagnostic Alert Status

INFO

INFO

Unit Information

MODEL

MODEL

Model Number

OS

OS

Operating System

RS

RS

Reset System

SN

SN

Serial Number

RESET

RESET

Reset Data

PASWD

PASWD

Enter Reset or Setup

Password

ENERG

ENERG

Reset Energy Accumulators

DEMND

DEMND

Reset Demand Maximums

User Interface (UI)
Menu Abbreviations
Defined

The user can set the display mode to either IEC or IEEE notation in the SETUP menu.