Veris Industries Badger 200 SERIES Install User Manual
Page 13

13
SPECIFICATIONS
Wetted Materials for all sensors
• (see ordering matrix)
Sensor Sleeve and Hex Adapter for 220BR, 225BR, and
226BR
• Sleeve: admiralty brass, UNS C44300; hex adapter: valve
bronze, UNS C83600
Sensor Sleeve and Hex Adapter for 220SS and 226SS
• Series 300 stainless steel
Temperature Ratings
• Standard version:
221 deg. F (105 deg. C) continuous service
• High temperature version:
285 deg. F (140.6 deg. C) continuous service
305 deg. F (150 deg. C) peak temperature (limited duration)
Pressure Ratings
At 100 deg. F
At 300 deg. F
220SS
400 psi
325 psi
220B
400 psi
325 psi
225B
300 psi
210 psi
226B
400 psi
250 psi
226SS
400 psi
300 psi
Recommended Design Flow Range
• 0.5 to 30 ft/sec
• Initial detection below 0.3 ft/sec
Accuracy
• ± 1.0% of full scale over recommended design flow range
Repeatability
• ± 0.3% of full scale over recommended design flow range
Linearity
• ± 0.2% of full scale over recommended design flow range
Transducer Excitation
• Quiescent current 600uA@8VDC to 35VDC max.
• Quiescent voltage (V
high
)
Supply Voltage -(600uA*Supply impedance)
• ON State (V
Low
) Max. 1.2VDC@40mA current limit
(15ohm+0.7VDC)
Output Frequency
• 3.2 Hz to 200 Hz
Output Pulse Width
• 5 msec ±25%
Electrical Cable for Standard Sensor Electronics
• 20 feet of 2-conductor 20 AWG shielded U.L. type PTLC
wire provided for connection to display or analog trans-
mitter unit. Rated to 105 deg. C. May be extended to a
maximum of 2000 feet with similar cable and insulation
appropriate for application.
Electrical Cable for IR Sensor Electronics
• 48 inches of U.L. Style 116666 copper solid AWG 18 wire
with direct burial insulation. Rated to 105 deg. C.