beautypg.com

Control power, Wiring (cont.), Direct connect control power (dc control power) – Veris Industries E50H5A Install User Manual

Page 9: Direct connect control power (line to neutral), Fuse recommendations

background image

ZL0117-0D

Page 9 of 28

©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 08131

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

Installation Guide

Power Monitoring

E50H2A, E50H5A

TM

Control Power

Direct Connect Control Power (DC Control Power)

L1

N

L2 L3

1 2

G

L1

N

L2 L3

1 2

G

L1

1 2

G

L2 L3

Direct Connect Control Power (Line to Neutral)

Line to Neutral from 90 VAC to 347 VAC (UL) or 300 VAC (CE)

1 2

G

Control Power Transformer (CPT) Connection

Direct Connect Control Power (Line to Line)

Line to Line from 90 VAC to 600 VAC (UL) (520 VAC for CE). In

UL installations the lines may be floating (such as a delta).
If any lines are tied to an earth (such as a corner grounded

delta), see the Line to Neutral installation limits. In CE

compliant installations, the lines must be neutral (earth)

referenced at less than 300 VAC

L-N

The Control Power Transformer may be wired L-N or L-L. Output to

meet meter input requirements

DC Control Power from 125 VDC to 300 VDC

(UL and CE max.)

Fuse Recommendations

Keep the fuses close to the power source (obey local and national code requirements).

For selecting fuses and circuit breakers, use the following criteria:

• Select current interrupt capacity based on the installation category and fault current capability.

• Select over-current protection with a time delay.

• Select a voltage rating sufficient for the input voltage applied.

• Provide overcurrent protection and disconnecting means to protect the wiring. For AC installations, use Veris AH02,

AH03, AH04, or equivalent. For DC installations, provide external circuit protection. Suggested: 0.5 A, time delay fuses.

• The earth connection is required for electromagnetic compatibility (EMC) and is not a protective earth ground.

L1

N

L2 L3

X2

X1

A

B

C

N

A

B

C

X2

X1

X2

X1

+

-

+

-

+

-

White

Black

White

Black

White

Black

Diagram 5: 3-Phase 4-Wire Wye Direct Voltage Input

Connection 3 CT

Use System Type 40 (3L + 1n)

White

Black

White

Black

White

Black

L1

N

L2 L3

X2

X1

A

B

C

N

A

B

C

X2

X1

X2

X1

+

-

+

-

+

-

Diagram 6: 3-Phase 4-Wire Wye Connection 3 CT

3 PT

Use System Type 40 (3L + 1n)

Wiring (cont.)