beautypg.com

Dimensions, English - continued – York UL R134A User Manual

Page 82

background image

JOHNSON CONTROLS

82

Dimensions –

English - continued

Models YCIV0357E/V and YCIV0397S/P

Notes:

1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance,

reliable operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpre-

dictable air patters and possible diminished performance. Johnson Controls’ unit controls will optimize the operation without nuisance

high pressure safety cutouts; however, the system designer MUST consider potential performance degradation.

Access to the unit control center stipulates the unit is no higher than on spring isolators. Recommended minimum clearances: side to wall

- 6’; rear to wall - 6’; control panel end to wall - 4’; top - no obstructions whatsoever; distance between adjacent units - 10’. No more than

one adjacent wall may be higher than the unit.

VIEW C-C

VIEW B-B

12"

CONTROL ENTRY

3" WIDE X 13 1/2" HIGH

1 1/2"

4"

POWER ENTRY

10" WIDE X 13" HIGH

1 3/4"

POWER ENTRY IS ON BOTTOM OF PANEL

88 1/8"

C

B

B

C

VIEW A-A