Temperature and flows, Si units) – York UL R134A User Manual
Page 11
JOHNSON CONTROLS
FORM 201.23-EG1 (1007)
11
TEMPERATURE AND FLOWS
(SI Units)
NOTES:
1. For leaving brine temperature below 4.4°C, contact your nearest Johnson Controls office for application requirements.
2. For leaving water temperature higher than 15.6°C, contact the nearest Johnson Controls office for application guidelines.
3. The evaporator is protected against freezing to -28.8°C with an electric heater as standard.
MODEL
NUMBER
YCIV
LEAVING WATER
TEMPERATURE (°C)
COOLER
3
FLOW
(l/s)
AIR ON CONDENSER (°C)
MIN.
1
MAX.
2
MIN.
MAX.
MIN.
MAX
50 Hz
60 Hz
0600(S/P)
0157(S/P)
4.4
15.6
8.8
42.6
-17.8
51.7
0590(E/V)
0157(E/V)
4.4
15.6
10.1
47.3
-17.8
51.7
0650(S/P)
0177(S/P)
4.4
15.6
10.1
47.3
-17.8
51.7
0630(E/V)
0177(E/V)
4.4
15.6
10.1
47.3
-17.8
51.7
0720(S/P/)
0187(S/P)
4.4
15.6
10.1
47.3
-17.8
51.7
0700(E/V)
0187(E/V)
4.4
15.6
10.1
47.3
-17.8
51.7
0760(E/V)
0197(E/V)
4.4
15.6
11.4
47.3
-17.8
51.7
0770(S/P)
0207(S/P)
4.4
15.6
11.4
50.5
-17.8
51.7
0800(E/V)
0207(E/V)
4.4
15.6
11.4
47.3
-17.8
51.7
0840(S/P)
0227(S/P)
4.4
15.6
11.4
50.5
-17.8
51.7
0830(E/V)
0227(E/V)
4.4
15.6
11.4
47.3
-17.8
51.7
0920(S/P)
0247(S/P)
4.4
15.6
11.4
50.5
-17.8
51.7
0930(E/V)
0247(E/V)
4.4
15.6
10.1
47.3
-17.8
51.7
1000(S/P)
0267(S/P)
4.4
15.6
11.4
50.5
-17.8
51.7
1050(E/V)
0267(E/V)
4.4
15.6
11.4
50.5
-17.8
51.7
1070(S/P)
0287(S/P)
4.4
15.6
15.8
75.7
-17.8
51.7
1120(E/V)
0287(E/V)
4.4
15.6
15.8
75.7
-17.8
51.7
1180(S/P)
0307(S/P)
4.4
15.6
18.9
75.7
-17.8
51.7
1220(E/V)
0327(E/V)
4.4
15.6
18.9
75.7
-17.8
51.7
1340(S/P)
0357(S/P)
4.4
15.6
18.9
75.7
-17.8
51.7
1380(E/V)
0357(E/V)
4.4
15.6
18.9
75.7
-17.8
51.7
1500(S/P)
0397(S/P)
4.4
15.6
18.9
75.7
-17.8
51.7