High efficiency ratings – York UL R134A User Manual
Page 38
JOHNSON CONTROLS
38
High Efficiency Ratings
.
–.
SI - 400V/50Hz
MODEL: YCIV0930E/V
AIR TEMPERATURE ON - CONDENSER (°C)
LCWT
25.0
30.0
35.0
40.0
45.0
46.0
(°C)
KWi
KWi
COP
KWi
KWi
COP
KWi
KWi
COP
KWi
KWi
COP
KWi
KWi
COP
KWi
KWi
COP
5.0
824.5
194.8
3.8
811.2
221.5
3.4
795.7
251.2
2.9
773.5
283.8
2.5
730.4
305.9
2.2
721.2
309.7
2.2
6.0
847.7
196.4
3.9
833.8
222.9
3.4
817.7
252.6
3.0
793.8
284.9
2.6
748.4
306.5
2.3
738.8
310.5
2.2
7.0
871.3
198.1
4.0
856.9
224.4
3.5
840.1
254.0
3.1
814.6
286.0
2.7
766.7
307.1
2.3
754.9
309.8
2.3
8.0
895.3
199.9
4.1
880.5
226.0
3.6
863.0
255.6
3.1
835.8
287.1
2.7
785.5
307.7
2.4
763.0
303.6
2.4
9.0
919.9
201.9
4.1
904.5
227.8
3.7
886.3
257.2
3.2
856.8
287.9
2.8
804.7
308.2
2.5
770.6
296.9
2.4
10.0
944.8
204.0
4.2
928.9
229.6
3.7
910.1
258.9
3.3
877.5
288.5
2.8
821.6
307.2
2.5
777.9
289.9
2.5
11.0
970.3
206.2
4.3
953.8
231.6
3.8
934.4
260.7
3.3
898.6
289.1
2.9
829.7
300.0
2.6
784.7
282.6
2.6
12.0
995.9
208.6
4.4
979.1
233.6
3.9
959.0
262.6
3.4
920.1
289.7
3.0
837.3
292.4
2.7
791.0
275.3
2.7
13.0
1022.2 210.5
4.4
1004.7 235.9
3.9
984.2
264.6
3.5
941.9
290.4
3.0
844.2
284.8
2.8
796.8
268.3
2.8
MODEL: YCIV1050E/V
AIR TEMPERATURE ON - CONDENSER (°C)
LCWT
25.0
30.0
35.0
40.0
45.0
46.0
(°C)
KWi
KWi
COP
KWi
KWi
COP
KWi
KWi
COP
KWi
KWi
COP
KWi
KWi
COP
KWi
KWi
COP
5.0
935.9
214.3
3.9
919.5
246.0
3.4
900.1
281.3
3.0
875.5
321.9
2.5
811.1
342.9
2.2
798.1
346.7
2.2
6.0
962.5
215.7
4.0
945.8
247.0
3.5
925.6
282.3
3.0
898.2
322.2
2.6
831.3
343.3
2.3
817.8
347.2
2.2
7.0
989.5
217.3
4.1
972.5
248.1
3.6
951.7
283.3
3.1
921.3
322.3
2.7
851.9
343.6
2.3
838.0
347.6
2.3
8.0
1017.1 219.1
4.2
999.6
249.4
3.7
978.3
284.3
3.2
944.1
322.3
2.7
872.7
343.8
2.4
858.7
347.9
2.3
9.0
1045.2 221.1
4.3
1027.4 250.9
3.7
1005.4 285.5
3.3
967.3
322.3
2.8
894.2
343.9
2.4
879.6
348.1
2.4
10.0
1073.8 223.4
4.4
1055.6 252.5
3.8
1033.0 286.9
3.3
991.0
322.2
2.9
915.8
344.0
2.5
901.0
348.2
2.4
11.0
1102.8 225.9
4.4
1084.4 254.3
3.9
1061.2 288.3
3.4
1015.0 322.2
2.9
938.0
344.0
2.6
922.6
348.2
2.5
12.0
1132.3 228.7
4.5
1113.6 256.4
4.0
1089.8 289.9
3.5
1039.3 322.2
3.0
960.5
344.0
2.6
944.8
348.2
2.5
13.0
1162.3 231.7
4.6
1143.3 258.7
4.1
1119.1 291.7
3.6
1063.8 322.3
3.1
983.3
344.0
2.7
967.4
348.1
2.6
MODEL: YCIV1120E/V
AIR TEMPERATURE ON - CONDENSER (°C)
LCWT
25.0
30.0
35.0
40.0
45.0
46.0
(°C)
KWi
KWi
COP
KWi
KWi
COP
KWi
KWi
COP
KWi
KWi
COP
KWi
KWi
COP
KWi
KWi
COP
5.0
996.2
225.3
4.0
979.2
259.7
3.4
959.5
298.8
3.0
935.5
344.4
2.5
869.0
364.4
2.2
855.4
367.7
2.2
6.0
1024.5 226.7
4.1
1007.0 260.4
3.5
986.4
299.5
3.0
960.5
344.8
2.6
890.3
364.4
2.3
876.3
367.9
2.2
7.0
1053.4 228.4
4.2
1035.3 261.3
3.6
1013.9 300.0
3.1
984.3
344.2
2.7
912.1
364.3
2.3
897.7
367.9
2.3
8.0
1082.9 230.4
4.2
1064.2 262.5
3.7
1042.0 300.7
3.2
1008.6 343.5
2.7
934.3
363.9
2.4
919.5
367.6
2.3
9.0
1112.9 232.7
4.3
1093.7 263.9
3.8
1070.7 301.6
3.3
1033.1 342.9
2.8
956.7
363.5
2.5
941.8
367.2
2.4
10.0
1143.5 235.4
4.4
1123.7 265.6
3.9
1100.0 302.8
3.4
1058.1 342.2
2.9
979.9
362.9
2.5
964.3
366.8
2.5
11.0
1174.4 238.5
4.5
1154.4 267.5
3.9
1129.9 304.0
3.4
1083.6 341.5
3.0
1003.4 362.3
2.6
987.4
366.2
2.5
12.0
1206.4 241.9
4.5
1185.5 269.8
4.0
1160.4 305.5
3.5
1109.5 340.9
3.0
1027.4 361.6
2.7
1011.0 365.5
2.6
13.0
1238.7 245.7
4.6
1217.3 272.4
4.1
1191.4 307.2
3.6
1135.6 340.4
3.1
1051.7 360.9
2.7
1034.9 364.8
2.7
NOTES:
1. kWo
= Unit kW Cooling Capacity Output
2. kWi
= Compressor kW Input
3. COP
= Coefficient of Performance (includes condenser fan power)
4. LCWT = Leaving Chilled Water Temperature
5. Ratings based on 0.168 l/s cooler water per ton, and 0.018 (m
2
– °C)/kW
6. ARI 550/590 does not provide certification for 50Hz ratings. The unique use of the YCIV variable speed drive allows compressor operation at the output speed regardless of the input
power frequency. This allows for common unit/heat exchanger configurations between 60Hz and 50Hz with closely matching capacity.