UNIT LOCATION
The YCIV chillers are designed for outdoor installation.

When selecting a site for installation, be guided by the

following requirements:

1. Installation sites may be either on a roof or on ground

level. (See FOUNDATION)

2. Select a place having an adequate supply of fresh air

for the condensers. Recommended clearances for all

units are shown on the DIMENSIONS pages.

3. Avoid locations near windows or structures where

normal operating sounds may be objectionable.

4. The standard condenser fans are propeller-type and

are not recommended for use with ductwork, filters

or other impedements to airflow in the condenser air

stream.

5. When it is desirable to surround the unit(s), it is rec-

ommended that the screening be able to pass the

required chiller CFM without exceeding 0.1" external

static pressure.

6. Protection against corrosive environments is available

by supplying the units with either copper fins, or cured

epoxy-coating on the condenser coils. Epoxy-coated

coils should be utilized with any units being installed at

the seashore, or where salt spray may hit the units, or

where acid rain is prevalent (copper condenser coils

are not recommended where they may be exposed

to acid rain).

7. On installations where winter operation is intended and

snow accumulations are expected, additional eleva-

tion must be provided to insure normal condenser air

flow.

FOUNDATION
The unit should be mounted on a flat and level founda-

tion, ground or roof, capable of supporting the entire

operating weight of the equipment. Please contact your

nearest Johnson Controls Sales Office for shipping and

operating weights.

Roof Locations – Adequate structural strength to safely

support the entire weight of the unit and service person-

nel must be provided. Care must be taken not to damage

the roof during installation. If the roof is “bonded”, consult

building contractor or architect for special installation re-

quirements. Roof installations should incorporate the use

of spring-type isolators to minimize the transmission of

vibration into building structure. Additional support should

be provided to the roof at the spring-isolator locations.

Ground Locations Units must be installed on a sub-

stantial base that will not settle and cause strain on the

refrigerant lines, resulting in possible leaks. A one-piece

concrete slab, with footers extending below the frost line,

is recommended. The slab should not be tied to the main

building foundation as noises will telegraph.

Mounting holes (5/8") are provided in the base rails for

bolting the unit to its foundation. See DIMENSIONS for

location of the mounting holes.

For ground installations, precautions should be taken to

protect the unit from tampering by, or injury to, unauthor-

ized persons. Fasteners on access panels will prevent

casual tampering; however, further safety precautions,

such as unit enclosure options, a fenced-in enclosure, or

locking devices on the panels may be advisable. Check

local authorities for safety regulations.

CHILLED LIQUID PIPING
The chilled liquid piping system should be laid out so that

the circulating pump discharges into the cooler. The inlet

and outlet cooler-liquid connections are given in DIMEN-

SIONS. Hand stop valves are recommended for use in

all lines to facilitate servicing. Drain connections should

be provided at all low points to permit complete drainage

of the cooler and system piping.

A strainer (40 mesh) is recommended for use on the INLET

line to the cooler, and must be in place at initial operation

of the water pumps.

Pressure-gauge connections are recommended for instal-

lation in the inlet and outlet water lines. Gauges are not

provided with the unit and are to be furnished by others.

Chilled liquid lines exposed to the weather should be

wrapped with a supplemental heater cable and insulated,

or glycol should be added to the chilled liquid to protect

against freezing if low-ambient periods are expected.

A flow switch is available as an accessory on all units. A

flow switch must be installed in the leaving water piping

of the cooler and must not be used to start and stop the

unit.

Application Data