Standard Efficiency YCIV_ _ _ _ S/P

Standard Efficiency YCIV_ _ _ _ S/P

Model No./Nameplate

System 1

System 2

Std. & Ultra Quiet Cond. Fans

High Head/Static Cond. Fans

Two-Speed Cond. Fans

Std. & Ultra Quiet Cond. Fans

High Head/Static Cond. Fans

Two-Speed Cond. Fans

YCIV S/P

Input Volts

(9)

Input Freq Compressor

RLA (5)

Condenser Fans

Compressor

Condenser Fans

Compressor

RLA (5)

Condenser Fans

Compressor

RLA (5)

Condenser Fans

Compressor

RLA (5)

Condenser Fans

Compressor

RLA (5)

Condenser Fans

Qty.

FLA (EA)

RLA (5)

Qty.

FLA (EA)

Qty.

FLA (EA)

Qty.

FLA (EA)

Qty.

FLA (EA)

Qty.

FLA (EA)

0157

460

60

120

4

2.8

120

4

2.8

380

60

152

4

3.5

152

4

9.3

152

4

3.5

152

4

9.3

0600

400

50

144

4

3.1

144

4

9.3

152

4

3.8

144

4

3.1

144

4

9.3

152

4

3.8

0177

460

60

159

4

2.8

105

4

2.8

380

60

201

4

3.5

201

4

9.3

133

4

3.5

133

4

9.3

0650

400

50

191

4

3.1

191

4

9.3

198

4

3.8

127

4

3.1

127

4

9.3

132

4

3.8

0187

460

60

162

5

2.8

120

4

2.8

380

60

205

5

3.5

205

5

9.3

152

4

3.5

152

4

9.3

0720

400

50

195

5

3.1

195

5

9.3

207

5

3.8

144

4

3.1

144

4

9.3

152

4

3.8

0207

460

60

145

5

2.8

162

4

2.8

380

60

184

5

3.5

184

5

9.3

206

4

3.5

206

4

9.3

0770

400

50

174

5

3.1

174

5

9.3

185

5

3.8

195

4

3.1

195

4

9.3

201

4

3.8

0227

460

60

162

5

2.8

162

5

2.8

380

60

205

5

3.5

205

5

9.3

205

5

3.5

205

5

9.3

0840

400

50

194

5

3.1

194

5

9.3

206

5

3.8

194

5

3.1

194

5

9.3

206

5

3.8

0247

460

60

193

6

2.8

160

5

2.8

380

60

245

6

3.5

245

6

9.3

203

5

3.5

203

5

9.3

0920

400

50

232

6

3.1

232

6

9.3

246

6

3.8

192

5

3.1

192

5

9.3

204

5

3.8

0267

460

60

191

6

2.8

191

6

2.8

380

60

242

6

3.5

242

6

9.3

242

6

3.5

242

6

9.3

1000

400

50

230

6

3.1

230

6

9.3

243

6

3.8

230

6

3.1

230

6

9.3

243

6

3.8

YCIV S/P

Control

KVA (7)

Unit Short Circuit Withstand (KA)

Field Wiring & Protection

Std. & Ultra Quiet Cond. Fans

High Head/High Static Fans

Two-Speed Cond. Fans

Terminal Block

(STD)

Circuit Breaker

(OPT)

Minimum Ckt.

Ampacity (MCA) (3)

Recommended

Fuse/Ckt. Breaker

Rating (4)

Max. Inverse Time

Ckt. Brkr. Rating (2)

Max Dual Element

Fuse Size (2)

Minimum Ckt. Am-

pacity (MCA) (3)

Recommended

Fuse/Ckt. Breaker

Rating (4)

Max. Inverse Time

Ckt. Brkr. Rating (2)

Max Dual Element

Fuse Size (2)

Minimum Ckt. Am-

pacity (MCA) (3)

Recommended

Fuse/Ckt. Breaker

Rating (4)

Max. Inverse Time

Ckt. Brkr. Rating (2)

Max Dual Element

Fuse Size (2)

0157

1.8

30KA

65KA

293

350

400

400

1.8

30KA

65KA

370

450

500

500

417

500

500

500

0600

1.8

30KA

65KA

350

400

450

450

373

450

500

500

399

450

500

500

0177

1.8

30KA

65KA

326

400

450

450

1.8

30KA

65KA

413

500

600

600

459

600

600

600

0650

1.8

30KA

65KA

390

450

500

500

410

500

600

600

440

500

600

600

0187

1.8

30KA

65KA

348

400

500

500

1.8

30KA

65KA

440

500

600

600

492

600

700

700

0720

1.8

30KA

65KA

416

500

600

600

445

500

600

600

472

600

600

600

0207

1.8

30KA

65KA

373

450

500

500

1.8

30KA

65KA

472

600

600

600

525

600

700

700

0770

1.8

30KA

65KA

446

500

600

600

471

600

600

600

502

600

700

700

0227

1.8

30KA

65KA

392

450

500

500

1.8

30KA

65KA

496

600

700

700

554

700

700

700

0840

1.8

30KA

65KA

468

600

600

600

502

600

700

700

530

600

700

700

0247

1.8

30KA

65KA

433

500

600

600

1.8

30KA

65KA

547

700

700

700

610

700

800

800

0920

1.8

30KA

65KA

517

600

700

700

553

700

800

800

585

700

800

800

0267

1.8

30KA

65KA

464

600

600

600

1.8

30KA

65KA

587

700

800

800

657

800

800

800

1000

1.8

30KA

65KA

555

700

700

700

593

700

800

800

629

700

800

800