MODEL: YCIV0600S/P

AIR TEMPERATURE ON - CONDENSER (°C)

LCWT

25.0

30.0

35.0

40.0

45.0

46.0

(°C)

KWi

KWi

COP

KWi

KWi

COP

KWi

KWi

COP

KWi

KWi

COP

KWi

KWi

COP

KWi

KWi

COP

5.0

528.8

133.1

3.6

520.9

152.2

3.2

511.8

172.8

2.8

497.4

196.1

2.4

462.2

214.6

2.0

455.0

218.5

2.0

6.0

543.2

134.0

3.7

535.0

152.9

3.2

525.5

173.7

2.8

509.5

196.7

2.4

473.3

215.3

2.1

465.8

219.2

2.0

7.0

557.9

134.9

3.8

549.4

153.8

3.3

539.5

174.5

2.9

521.7

197.3

2.5

484.5

216.0

2.1

476.8

219.9

2.0

8.0

572.9

135.8

3.8

564.1

154.6

3.4

553.7

175.4

2.9

533.9

197.9

2.5

495.5

216.9

2.2

487.9

220.6

2.1

9.0

588.0

136.8

3.9

578.9

155.6

3.4

568.2

176.3

3.0

546.3

198.5

2.6

507.2

217.5

2.2

499.2

221.3

2.1

10.0

603.4

137.9

4.0

594.1

156.6

3.5

583.0

177.3

3.1

558.9

199.1

2.6

519.0

218.1

2.2

510.8

222.0

2.2

11.0

619.1

139.1

4.1

609.5

157.6

3.6

598.0

178.4

3.1

571.6

199.7

2.7

531.0

218.7

2.3

522.6

222.6

2.2

12.0

635.0

140.3

4.1

625.1

158.7

3.6

613.2

179.4

3.2

584.5

200.3

2.7

542.9

219.3

2.3

532.1

221.1

2.3

13.0

651.2

141.6

4.2

641.0

159.8

3.7

628.7

180.5

3.2

597.5

201.0

2.8

555.1

219.9

2.4

537.5

215.9

2.3

MODEL: YCIV0650S/P

AIR TEMPERATURE ON - CONDENSER (°C)

LCWT

25.0

30.0

35.0

40.0

45.0

46.0

(°C)

KWi

KWi

COP

KWi

KWi

COP

KWi

KWi

COP

KWi

KWi

COP

KWi

KWi

COP

KWi

KWi

COP

5.0

587.3

146.6

3.7

576.4

167.9

3.2

563.2

190.9

2.8

536.0

208.9

2.4

491.4

218.9

2.1

462.3

206.9

2.1

6.0

603.7

147.6

3.8

592.6

168.9

3.3

579.1

192.0

2.8

550.1

209.5

2.5

496.5

214.8

2.2

467.9

203.3

2.2

7.0

620.4

148.6

3.8

609.2

169.9

3.3

595.2

193.1

2.9

563.9

210.0

2.5

502.4

210.9

2.2

474.0

199.7

2.2

8.0

637.4

149.7

3.9

626.0

170.9

3.4

611.2

193.9

3.0

577.7

210.4

2.6

508.8

207.2

2.3

479.4

195.7

2.3

9.0

654.7

150.8

4.0

643.0

171.9

3.5

626.8

194.3

3.0

591.8

210.7

2.6

514.8

203.2

2.4

484.4

191.6

2.4

10.0

672.0

152.0

4.1

660.4

173.1

3.5

642.6

194.8

3.1

605.9

211.0

2.7

520.5

199.0

2.5

488.9

187.6

2.4

11.0

689.4

153.4

4.1

677.8

174.4

3.6

658.6

195.3

3.2

620.3

211.4

2.8

525.7

194.9

2.5

493.2

183.6

2.5

12.0

707.1

154.9

4.2

695.4

175.6

3.7

674.7

195.8

3.2

634.8

211.7

2.8

530.6

190.8

2.6

497.4

179.6

2.6

13.0

725.1

156.4

4.3

713.3

177.0

3.7

691.0

196.4

3.3

649.5

212.0

2.9

534.7

186.7

2.7

501.5

175.7

2.7

MODEL: YCIV0720S/P

AIR TEMPERATURE ON - CONDENSER (°C)

LCWT

25.0

30.0

35.0

40.0

45.0

46.0

(°C)

KWi

KWi

COP

KWi

KWi

COP

KWi

KWi

COP

KWi

KWi

COP

KWi

KWi

COP

KWi

KWi

COP

5.0

639.4

158.1

3.7

628.8

180.6

3.2

616.7

205.2

2.8

594.6

230.0

2.4

551.9

245.6

2.1

543.3

248.7

2.1

6.0

657.2

159.2

3.8

646.3

181.6

3.3

633.7

206.2

2.9

608.9

230.4

2.5

564.8

246.2

2.2

556.2

249.2

2.1

7.0

675.3

160.5

3.9

664.0

182.7

3.4

651.0

207.3

2.9

623.5

230.8

2.5

578.2

246.7

2.2

569.2

249.7

2.2

8.0

693.7

161.8

3.9

682.0

183.9

3.4

668.4

208.5

3.0

638.4

231.1

2.6

591.9

247.1

2.3

582.6

250.2

2.2

9.0

712.5

163.2

4.0

700.4

185.1

3.5

686.2

209.8

3.1

653.5

231.5

2.7

605.8

247.4

2.3

596.2

250.6

2.2

10.0

731.6

164.7

4.1

719.0

186.5

3.6

704.3

211.0

3.1

668.7

231.8

2.7

619.9

247.8

2.4

605.6

247.6

2.3

11.0

751.0

166.3

4.1

738.0

187.9

3.6

722.8

212.3

3.2

683.9

232.2

2.8

634.3

248.1

2.4

610.8

241.4

2.4

12.0

770.7

168.0

4.2

757.3

189.4

3.7

741.6

213.7

3.2

699.5

232.6

2.8

648.9

248.4

2.5

616.4

235.6

2.5

13.0

790.7

169.9

4.3

776.9

191.0

3.8

760.7

215.3

3.3

715.3

233.0

2.9

660.2

246.2

2.5

621.8

229.7

2.5

NOTES:

1. kWo

= Unit kW Cooling Capacity Output

2. kWi

= Compressor kW Input

3. COP

= Coefficient of Performance (includes condenser fan power)

4. LCWT = Leaving Chilled Water Temperature

5. Ratings based on 0.168 l/s cooler water per ton, and 0.018 (m

2

– °C)/kW

6. ARI 550/590 does not provide certification for 50Hz ratings. The unique use of the YCIV variable speed drive allows compressor operation at the output speed regardless of the input

power frequency. This allows for common unit/heat exchanger configurations between 60Hz and 50Hz with closely matching capacity.