FORM 160.55-O1 (604)

91

YORK INTERNATIONAL

MASTER SLOT NUMBERS LIST FOR USE WITH TREND FEA TURE

SLOT
NO.

DESCRIPTION

256 System: Chiller State

257 System: Coastdown Time Remaining

258 System: Prelube Time Remaining

259 System: Are Safety Shut down Contacts Closed

260 System: Are Cy cling Shutdown Contacts Closed

261 System: Are An tic i pa to ry Alarm Contacts Closed

262 System: Operating Hours

264 System: Number of Starts

265 System: Is Stop Switch Closed

266 System: Is Start Switch Closed

267 System: Is Remote Ready to Start

280 External Contact: Is Re mote Stop Closed

281 External Contact: Is Re mote Start Closed

282 External Contact: Is MultiUnit Cycling Closed

283 External Contact: Is Re mote Cycling Closed

284 External Contact: Is Aux il ia ry Safety Open

285 Jumper: Is Anti-Recycle Enabled

286 Jumper: Coastdown Operation

287 Jumper: Is Di ag nos tics Enabled

288 Jumper: Liquid Type

289 Jumper: Chilled Liq uid Pump Operation

290 Jumper: Motor Type

291 Jumper: Power Fail ure Restart

292 Jumper: Pre-Run Op er a tion

293 Jumper: Refrigerant Selection

294 Jumper: VSD Motor Sup ply Line Frequency

304 Options: Control Mode

305 Options: System Lan guage

307 Options: Display Mode

512 Sched: Is Schedule Enabled

1280 Pre-Rotation Vanes: Is Motor Switch Closed

1281 Pre-Rotation Vanes: Position

1282 Pre-Rotation Vanes: Are Vanes Opening

1283 Pre-Rotation Vanes: Are Vanes Closing

1284 Pre-Rotation Vanes: Are Vanes Holding

1285 Pre-Rotation Vanes: Control Mode

1296 Discharge: Temperature

1536 Oil: Differential Pressure

1537 Oil: Sump Temperature

1538 Oil Pump: Control Mode

1539 Oil Pump: Is Pump On

1540 Oil Pump: Manual Time Left

SLOT
NO.

DESCRIPTION

1792 Leaving Chilled Liquid: Temperature

1793 Leaving Chilled Liquid: Temperature Differential

1794 Leaving Chilled Liquid: Is Flow Switch Closed

1795 Leaving Chilled Liquid: Is Pump On

1796 Leaving Chilled Liquid: Local Temperature Setpoint

1797 Leaving Chilled Liquid: Remote Analog Tem per a ture

Setpoint

1798 Leaving Chilled Liquid: Remote ISN Temperature

Setpoint

1799 Leaving Chilled Liquid: Remote Modem Tem per a ture

Setpoint

1800 Leaving Chilled Liquid: Selected Temperature

Setpoint

1801 Leaving Chilled Liquid: Control Sensitivity

1802 Leaving Chilled Liquid: Remote Temperature

Range

1803 Leaving Chilled Liquid: Restart Temperature Off set

1804 Leaving Chilled Liquid: Restart Temperature

Setpoint

1805 Leaving Chilled Liquid: Shutdown Temperature Off-

set

1806 Leaving Chilled Liquid: Shutdown Temperature

Setpoint

1807 Return Chilled Liquid: Temperature

1808 Evaporator: Pressure

1809 Evaporator: Saturation Temperature

1810 Evaporator: Small Temperature Difference

1811 Evaporator: Is Refrigerant Sensor Present

1812 Evaporator: Refrigerant Temperature

1813 Evaporator: Delta P / P

1814 Evaporator: Brine Low Cutout

1815 Smart Freeze Protection: Is Control Enabled

1818 Leaving Chilled Liquid: Remote Digital Tem per a ture

Setpoint

2048 Leaving Condenser Liquid: Temperature

2049 Leaving Condenser Liquid: Is Flow Switch Closed

2050 Leaving Condenser Liquid: Is Pump On

2051 Return Condenser Liquid: Temperature

2052 Condenser: Pressure

2053 Condenser: Saturation Temperature

2054 Condenser: Small Temperature Difference

2057 Condenser: Is High Pressure Switch Closed

2058 Condenser: High Pressure Warning Threshold