beautypg.com

Setup screen – York R123 User Manual

Page 60

background image

YORK INTERNATIONAL

60

FORM 160.55-O1 (604)

SETUP SCREEN

OVERVIEW

This screen is the top level of the general con Þ g u ra tion
pa ram e ters. It allows programming of the time and
date, along with speciÞ cations as to how the time will
be dis played (12 or 24 hour format). In addition, the
chill er con Þ g u ra tion, as determined by the state of the
Microboard Program Jump ers and Program Switches
is dis played. A qualiÞ ed Service Technician, follow-
ing in struc tions in YORK Service Man u al 160.55-M1,
es tab lish es this con Þ g u ra tion per the desired operation.
This screen also serves as a gateway to more subscreens
for de Þ n ing general sys tem parameters

DISPLAY ONLY

031-01730-000 Microboard
Chilled Liquid Pump Operation:
Displays Standard or Enhanced

Motor Type:
Displays Fixed Speed or Variable Speed

Refrigerant Selection:
Displays R-11 or R123

Anti-Recycle:
Displays Disabled or Enabled

Power Failure Restart:
Displays Manual or Automatic

Liquid Type:
Displays Water or Brine

Coastdown:
Displays Standard (150 seconds) or En hanced (15
minutes – Steam Turbine applications)

Pre-Run:
Displays Standard (30 seconds) or Ex tend ed (180
sec onds)

Power Line Frequency (VSD only):
Displays 60 Hz or 50 Hz

031-02430-000 Microboard

Refrigerant Selection
Displays R11 or R123

Liquid Type
Displays Water or Brine

LD09562

FIG. 26

OptiView Control Center

This manual is related to the following products: