Printers, Fig. 44 – sample printout (status), York update chiller id 0 york update chiller id – York R123 User Manual

Page 116

background image

YORK INTERNATIONAL

116

FORM 160.55-O1 (604)

YORK UPDATE
CHILLER ID 0
YORK Update Chiller ID

-------------------------------------------------------------------------

(c) 1997 – 2001 YORK INTERNATIONAL
CORPORATION

SYSTEM RUN

LEAVING CHILLED LIQUID CONTROL

WARNING – PURGE – FLOAT SWITCH ERROR

[List all warnings presently active]

Controls C.MLM.02.03.102

Run Time 0 Days 2 Hr 59 Min

Operating Hours = 298 Hr

Number Of Starts = 106

Control Source = Local

Evaporator

-------------------------------------------------------------------------

Leaving Chilled Active Setpoint = 45.0 ~F

Chilled Liquid Pump = Run

Chilled Liquid Flow Switch = Closed

Leaving Chilled Liquid Temperature = 50.0 ~F

Return Chilled Liquid Temperature = 59.3 ~F

Evaporator Pressure = 7.2 Psia

Evaporator Saturation Temperature = 41.1 ~F

Evaporator Refrigerant Temperature = 40.0 ~F

[If Refrigerant Sensor enabled]

Small Temperature Difference = 10.0 ~F

Condenser

-------------------------------------------------------------------------

Condenser Liquid Pump = Run

Condenser Liquid Flow Switch = Closed

Leaving Condenser Liquid Temperature = 85.0 ~F

Return Condenser Liquid Temperature = 94.9 ~F

Condenser Pressure = 13.8 Psia

Condenser Saturation Temperature = 71.7 ~F

Small Temperature Difference = -13.3 ~F

Drop Leg Refrigerant Temperature = 85.0 ~F

[If Drop Leg Sensor enabled]

Sub Cooling Temperature = 2.0 ~F

[If Drop Leg Sensor enabled]

Compressor

-------------------------------------------------------------------------

Discharge Temperature = 121.6 ~F

Vent Line Solenoid = On

Oil Sump

-------------------------------------------------------------------------

Oil Pump Run Output = On

Oil Pressure = 30.7 Psid

Oil Sump Temperature = 137.9 ~F

[Skip the following section if Hot Gas Bypass is not

enabled]

Hot Gas

-------------------------------------------------------------------------

FIG. 44 – SAMPLE PRINTOUT (STATUS)

Valve Position = 15 %

Pre-Rotation Vanes Position = 75 %

Surge

-------------------------------------------------------------------------

Total Surge Count = 127

Surge Window Time = 1 Min

Surge Window Count = 0

[Skip the following section if Liquid Level is not

enabled]

Refrigerant Level Control

-------------------------------------------------------------------------

Refrigerant Level Position = 35 %

Ramp Up Time Remaining = 15 Sec

[If Ramp Up in effect]

Purge Control

-------------------------------------------------------------------------

Pressure = 42.8 Psia

Exhaust Count = 0

Exhaust Window = 60 Min

[Skip the following section if Motor Type is not EM]

Electro-Mechanical Starter

-------------------------------------------------------------------------

Motor Run = On

% Full Load Amps = 94 %

[Skip the following section if Motor Type is not Mod A

SSS]

Liquid-Cooled Solid State Starter

-------------------------------------------------------------------------

Motor Run = On

% Full Load Amps = 94 %

Phase A Voltage = 447 V

Phase B Voltage = 409 V

Phase C Voltage = 442 V

Phase A Current = 193 A

Phase B Current = 204 A

Phase C Current = 190 A

[Skip the following section if Motor Type is not Mod B

SSS]

Liquid-Cooled Solid State Starter

-------------------------------------------------------------------------

Motor Run = On

% Full Load Amps = 94 %

Starter Model = 33L

KW Hours = 20723 KWH

Input Power = 145 KW

Phase A Voltage = 447 V

Phase B Voltage = 409 V

Phase C Voltage = 442 V

Phase A Current = 193 A

Phase B Current = 204 A

Printers