Fig. 48 – sample printout (history report) – York R123 User Manual

Page 121

background image

FORM 160.55-O1 (604)

121

YORK INTERNATIONAL

3

YORK HISTORY 1
CHILLER ID 0

---------------------------------------------------------------------------

© 1997 - 1999 YORK INTERNATIONAL COR

PO

RA

TION

MSYSTEM READY TO START

LCSSS – LOGIC BOARD POWER SUPPLY

[List any warnings that were active at the time of

shutdown]

Controls C.MLM.02.03.102

Run Time 0 Days 2 Hr 59 Min

Operating Hours = 294 Hr

Number Of Starts = 105

Control Source = Local

Evaporator

---------------------------------------------------------------------------

Leaving Chilled Active Setpoint = 45.0 ~F

Chilled Liquid Pump = Stop

Chilled Liquid Flow Switch = Open

Leaving Chilled Liquid Temperature = 50.0 ~F

Return Chilled Liquid Temperature = 59.3 ~F

Evaporator Pressure = 7.2 Psia

Evaporator Saturation Temperature = 41.1 ~F

Evaporator Refrigerant Temperature = 40.0 ~F

[If Refrigerant Sensor enabled]

Small Temperature Difference = 10.0 ~F

Condenser

---------------------------------------------------------------------------

Condenser Liquid Pump = Stop

Condenser Liquid Flow Switch = Open

Leaving Condenser Liquid Temperature = 85.0 ~F

Return Condenser Liquid Temperature = 94.9 ~F

Condenser Pressure = 13.8 Psia

Condenser Saturation Temperature = 71.7 ~F

Small Temperature Difference = -13.3 ~F

Drop Leg Refrigerant Temperature = 85.0 ~F

[If Drop Leg Sensor enabled]

Sub Cooling Temperature = 2.0 ~F

[If Drop Leg Sensor enabled]

Compressor

---------------------------------------------------------------------------

Discharge Temperature = 121.6 ~F

Vent Line Solenoid = Off

Oil Sump

---------------------------------------------------------------------------

Oil Pump Run Output = Off

Oil Pressure = 0.0 Psid

Oil Sump Temperature = 137.9 ~F

[Skip the following section if Hot Gas Bypass is not

enabled]

Hot Gas

---------------------------------------------------------------------------

FIG. 48 – SAMPLE PRINTOUT (HISTORY REPORT)

Valve Position [If Hot Gas enabled] = 0 %

Pre-Rotation Vanes Position = 0 %

Surge

---------------------------------------------------------------------------

Total Surge Count = 127

Surge Window Time = 1 Min

Surge Window Count = 0

[Skip the following section if Liquid Level is not

enabled]

Refrigerant Level Control

---------------------------------------------------------------------------

Refrigerant Level Position = 35 %

Ramp Up Time Remaining = 15 Sec

[If Ramp Up in effect]

Purge Control

---------------------------------------------------------------------------

Pressure = 42.8 Psia

Exhaust Count = 0

Exhaust Window = 60 Min

[Skip the following section if Motor Type is not EM]

Electro-Mechanical Starter

---------------------------------------------------------------------------

Motor Run = Off

% Full Load Amps = 0 %

[Skip the following section if Motor Type is not Mod A

SSS]

Liquid-Cooled Solid State Starter

---------------------------------------------------------------------------

Motor Run = Off

% Full Load Amps = 0 %

Phase A Voltage = 447 V

Phase B Voltage = 409 V

Phase C Voltage = 442 V

Phase A Current = 0 A

Phase B Current = 0 A

Phase C Current = 0 A

[Skip the following section if Motor Type is not Mod B

SSS]

Liquid-Cooled Solid State Starter

---------------------------------------------------------------------------

Motor Run = Off

% Full Load Amps = 0 %

Starter Model = 33L

KW Hours = 20723 KWH

Input Power = 145 KW

Phase A Voltage = 447 V

Phase B Voltage = 409 V

Phase C Voltage = 442 V

Phase A Current = 0 A

Phase B Current = 0 A