beautypg.com

York YCAL0041 User Manual

Page 78

background image

YORK INTERNATIONAL

78

water sensors, and liquid line components (solenoid

valves, filter driers, sight glasses, and TXVs), as

discrete elements of a complete factory system.

Contractor shall be field erect system and provide

interconnecting refrigerant piping and wiring in

accordance with Manufacturer recommendations,

and project plans and schedules. Where not oth-

erwise specified, Contractor provided system piping

shall be in accordance with applicable sections of

ASHRAE Handbook.

O. Hot Gas By-Pass: Permits continuous, stable op-

eration at capacities below the minimum step of

unloading to as low as 5% capacity (depending on

both the unit & operating conditions) by introducing

an artificial load on the cooler. Hot gas by-pass is

installed on only one refrigerant circuit (System

#1).

P. Microprocessor Membrane Keypad Graphics on in

lieu of Standard English:

1. French language.

2. German language.

3. Spanish language.

4. Italian language.

Q. Thermal Storage: Leaving chilled liquid setpoint

range for charge cycle from 25°F to 20°F minimum,

with automatic reset of the leaving brine temperature

up to 40°F above the setpoint. (Works with Option

T)

R. Low Temperature Process Brine: Leaving chilled

liquid setpoint range 20°F to 30°F.

S. Chicago Code Relief Valves to meet Chicago Code

requirements.

T. Building Automation System (EMS) Reset Interface:

Chiller to accept 4 to 20mA, 0 to 10 VDC, or discrete

contact closure input to reset the leaving chilled

liquid temperature.

U. Remote Control Panel (Field-mounted): Auxiliary

panel for remote user interface for functions nor-

mally made at the unit control center. Available on

YCAL0014-0080 models.

V. OptiView Remote Control Panel (Field-mounted):

Graphical interface panel to remotely control and

monitor up to 8 different units.

W. Multi-Unit Sequencing Panel (Field-mounted):

Separate Sequencing control center is provided to

permit control of up to eight chillers in parallel based

on mixed liquid temperature.

X. Sound Reduction (Factory-mounted):

1. Ultra quiet, low speed, reduced noise fans

2. Compressor Acoustic Sound Blankets

Y. Vibration Isolation (Field-mounted):

1. Neoprene Pad Isolators.

2. 1 Inch Deflection Spring Isolators: Level ad-

justable, spring and cage type isolators for

mounting under the unit base rails.

3. 2 Inch Deflection Seismic Isolators: Level ad-

justable, restrained mounts in rugged welded

steel housing with vertical and horizontal limit

stops. Housings shall be designed to withstand

a minimum 1.0g accelerated force in all direc-

tions to 2 inches.

PART 3 - EXECUTION

3.01 INSTALLATION

A. General: Rig and Install in full accordance with

Manufacturers requirements, Project drawings, and

Contract documents.

B. Location: Locate chiller as indicated on drawings,

including cleaning and service maintenance clear-

ance per Manufacturer instructions. Adjust and level

chiller on support structure. If equipment provided

exceeds height of scheduled chiller, installing con-

tractor is responsible for additional costs associated

with extending the height of parapet or screening

walls/enclosures

C. Components: Installing Contractor shall provide and

install all auxiliary devices and accessories for fully

operational chiller.

D. Electrical: Coordinate electrical requirements and

connections for all power feeds with Electrical Con-

tractor (Division 16).

E. Controls: Coordinate all control requirements and

connections with Controls Contractor.

F. Finish: Installing Contractor shall paint damaged and

abraded factory finish with touch-up paint matching

factory finish.

This manual is related to the following products: