YORK INTERNATIONAL

5

FORM 150.64-EG1

MILLENNIUM CONTROL CENTER

All controls are contained in a NEMA 3R/12 (and

equivalent to IP55*) cabinet with hinged outer door and

includes:

Liquid Crystal Display with Light Emitting Diode back-

lighting for outdoor viewing:

Two display lines

Twenty characters per line

Color coded 12-button non-tactile keypad with sections

for:
DISPLAY/PRINT of typical information:

Chilled liquid temperatures

Ambient temperature

System pressures (each circuit)

Operating hours and starts (each compressor)

Print

calls up to the liquid crystal display:

Operating data for the systems

History of fault shutdown data for up to

the last six fault shutdown conditions

An RS-232 port, in conjunction with this

press-to-print button, is provided to permit

the capability of hard copy print-outs via a

separate printer (by others).

ENTRY section to:

ENTER setpoints or modify system values

SETPOINTS updating can be performed to:

Chilled liquid temperature setpoint and range

Remote reset temperature range

Set daily schedule/holiday for start/stop

Manual override for servicing

Low and high ambient cutouts

Number of compressors

Low liquid temperature cutout

Low suction pressure cutout

High discharge pressure cutout

Anti-recycle timer (compressor start cycle

time)

Anti-coincident timer (delay compressor

starts)

UNIT section to:

Set time

Set unit options

UNIT ON/OFF switch

The microprocessor control center is capable of dis-

playing the following:

• Return and leaving liquid temperature
• Low leaving liquid temperature cutout setting
• Low ambient temperature cutout setting
• Outdoor air temperature
• English or Metric data
• Suction pressure cutout setting
• Each system suction pressure
• Discharge pressure (optional)
• Liquid Temperature Reset via a YORK ISN DDC or

Building Automation System (by others) via:

- a pulse width modulated (PWM) input as stan-

dard

- a 4-20 milliamp or 0 -10 VDC input, or contact
closure with the optional B.A.S. interface option
• Anti-recycle timer status for each system
• Anti-coincident system start timer condition
• Compressor run status
• No cooling load condition
• Day, date and time
• Daily start/stop times
• Holiday status
• Automatic or manual system lead/lag control
• Lead system definition
• Compressor starts & operating hours
(each compressor)
• Status of hot gas valves, evaporator heater
and fan operation
• Run permissive status
• Number of compressors running
• Liquid solenoid valve status
• Load & unload timer status
• Water pump status

* Intensity of Protection European Standard

This manual is related to the following products: