YORK INTERNATIONAL

77

FORM 150.64-EG1

of N.E.C.) can be supplied to isolate the unit

power voltage for servicing. Separate external

fusing must be supplied, by others, in the in

coming power wiring, which must comply with

the National Electric Code and/or local codes.

4. Single Point Disconnect with Individual System

Breakers: Single point Terminal Block with Non-

Fused Disconnect and lockable external handle

(in compliance with Article 440-14 of N.E.C.)

can be supplied to isolate power voltage for

servicing. Factory interconnecting wiring from

disconnect to factory supplied circuit breakers.

Available on YCAL0041-0065.

5. Single Point Circuit Breaker: Single point Ter-

minal Block with Circuit Breaker and lockable

external handle (in compliance with Article 440

14 of N.E.C.) can be supplied to isolate power

voltage for servicing. Incoming power wiring

must comply with the National Electric Code

and/or local codes. Single Point Circuit Break

ers available on YCAL0041-0065 models.

D. Pressure Transducers and Readout Capability

1. Discharge Pressure Transducers: Permits unit

to sense and display discharge pressure. Stan-

dard on YCAL0080-0134 models.

E. Control Power Transformer: Converts unit power

voltage to 120-1-60 (500 VA capacity). Factory-

mounting includes primary and secondary wiring

between the transformer and the control panel.

F. Motor Current Module: Capable of monitoring com-

pressor motor current. Provides extra protection

against compressor reverse rotation, phase-loss

and phase imbalance. Option consists of one mod-

ule per electrical system. (Factory-mounted.)

G. Power Factor Correction Capacitors: Provided to

correct unit compressor factors to a 0.90-0.95.

H. Condenser Coil Environmental Protection:
1. Pre-Coated: Epoxy coated aluminum fin stock to

guard from corrosive agents and insulate

against galvanic potential. For mild seashore

or industrial locations.

2. Copper Fin: Provide copper fins in lieu of alumi-

num.
3. Post-Coated Dipped: Dipped-cured coating on

condenser coils for seashore and other corro-

sive applications (with the exception of strong

alkalis, oxidizers, and wet bromine, chlorine and

fluorine in concentrations greater than

100ppm).

I. Protective Chiller Panels (Factory or Field Mounted
1. Louvered Panels (condenser coils only):

Painted steel as per remainder of unit cabinet,

over external condenser coil faces.

2. Wire Panels (full unit): Heavy gauge, welded

wire-mesh, PVC -coated to resist corrosion, to pro-

tect condenser coils from incidental damage

and restrict unauthorized access to internal

components.

3. Louvered Panels (full unit): Painted steel as per

remainder of unit cabinet, to protect condenser

coils from incidental damage, visually screen

internal components, and prevent unauthorized

access to internal components.

4. Louvered/Wire Panels: Louvered steel panels

on external condenser coil faces, painted as

per remainder of unit cabinet. Heavy gauge,

welded wire-mesh, coated to resist corrosion,

around base of machine to restrict unauthorized

access.

J. Flow Switch (Field-mounted): Vapor proof SPDT,

NEMA 4X switch ( ___150 PSIG or ___300 PSIG),

-20°F to 250°F.

K. Differential Pressure Switch: Alternative to an

above mentioned flow switch. Pretempco model

DPS300A-P40PF-82582-5 (300 psi max. working

pressure) SPDT 5 amp 125/250VAC switch, Range

0 - 40 PSID, deadband 0.5 - 0.8 psi, with 1/4” NPTE

Pressure Connections.

L. Evaporator options:

1. Provide 1½" cooler insulation in lieu of standard

¾".

2. Provide DX Cooler with 300 PSIG water-side

design working pressure in lieu of standard 150

PSIG.

3. Provide Raised Face Flanges for field instal-

lation on cooler nozzles and field piping:

a. 150 PSIG, welded Flanges.

b. 300 PSIG, welded Flanges.

M. Service Isolation valves: Service suction and dis

charge (ball type) isolation valves are added to unit

per system. This option also includes a system high

pressure relief valve in compliance with ASHRAE

15. (Factory-mounted.)

N. Remote Cooler: Manufacturer shall provide sep-

arately: chiller less evaporator, leaving and return