York YCAL0041 User Manual
Page 67
YORK INTERNATIONAL
67
FORM 150.64-EG1
MODEL
YCAL
VOLT
MCA
1
MIN
N/F DISC
SW
2
D.E. FUSE
CKT. BKR.
5
FIELD WIRING LUGS
6
FIELD WIRING LUGS
6
FIELD WIRING LUGS
6
SYSTEM #1 COMPRESSOR & FAN
SYSTEM #2 COMPRESSOR & FAN
TERMINAL BLOCK (std)
NF DISC. SWITCH (opt)
CIRCUIT BREAKER (opt)
COMPR. #1
COMPR. #2
FANS
COMPR. #1
COMPR. #2
FANS
REC. MAX
4
REC.
MAX LUGS/
PHASE
LUG WIRE RANGE
LUGS/
PHASE
LUG WIRE RANGE
LUGS/
PHASE
LUG WIRE RANGE
RLA
LRA
RLA
LRA
QTY FLA
(EA)
RLA
LRA
RLA
LRA
QTY FLA
(EA)
0041
380/415
90
100
100
100
100
100
1
6awg - 500MCM
1
6awg - 350MCM
1
6awg - 350MCM
17.2
125
17.2
125
2
4
17.2
125
17.2
125
2
4
0045
380/415
91
100
100
100
100
100
1
6awg - 500MCM
1
6awg - 350MCM
1
6awg - 350MCM
17.6
125
17.6
125
2
4
17.2
125
17.2
125
2
4
0051
380/415
103
150
110
110
110
110
1
6awg - 500MCM
1
6awg - 350MCM
1
6awg - 350MCM
17.6
158
17.6
158
2
4
21.8
127
23.7
187
2
4
0055
380/415
113
150
125
125
125
125
1
6awg - 500MCM
1
6awg - 350MCM
1
6awg - 350MCM
23.7
187
21.8
127
2
4
21.8
127
23.7
187
2
4
0061
380/415
124
150
150
150
150
150
1
6awg - 500MCM
1
6awg - 350MCM
1
6awg - 350MCM
30.1
225
23.7
198
2
4
23.7
167
23.7
167
2
4
0065
380/415
132
150
150
150
150
150
1
6awg - 500MCM
1
6awg - 350MCM
1
6awg - 350MCM
30.1
225
30.1
225
2
4
23.7
198
23.7
198
2
4
YCAL0041 - YCAL0065
SINGLE POINT FIELD SUPPLIED POWER WIRING (See Fig. 2)
(One Field Provided Power Supply to the chiller. Field connections to Factory Provided Power Terminal Block (standard), Non-Fused Discon-
nect Switch (optional) or Circuit Breaker (optional).)