Dimensions - ycal0045 (english), Dimensions, Ycal0045 (english) – York YCAL0041 User Manual

Page 36

background image

YORK INTERNATIONAL

36

Dimensions -

YCAL0045 (English)

VIEW B-B

3 15/16"

3 1/4"

6 3/4"

BOTTOM OF PANEL

7/8" TYP.

47 3/4"

46 15/16"

45 1/8"

12 5/8"

3" VICTAULIC (typ)

90 1/4" BASE WIDTH

LEFT END

LIQUID OUT

34 5/8"

15 3/4"

9 15/16"

ELECTRICAL ACCESS
PANEL

LIQUID IN

Aluminum

Copper

YCAL

Center of Gravity (in.)

YCAL

Center of Gravity (in.)

X

Y

X

Y

0045

59.2

43.5

0045

63.2

43.7

NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reli-

able operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable

airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety

cutouts; however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall

– 6'; rear to wall – 6'; cooler end to wall – 4'0"; coil end to wall - 6'; top – no obstructions allowed; distance between adjacent units – 10'.

No more than one adjacent wall may be higher than the unit. 1" nominal deflection isolators (not shown) will increase overall unit height by

6".