Dimensions - ycal0065 (english), Dimensions, Ycal0065 (english) – York YCAL0041 User Manual
Page 44
YORK INTERNATIONAL
44
Dimensions -
YCAL0065 (English)
62 5/8"
61 7/8"
34 11/16"
15 3/4"
9 15/16"
43 1/8"
12 5/8"
3" VICTAULIC (typ)
ELECTRICAL ACCESS
PANEL
90 1/4" BASE WIDTH
LEFT END
LIQUID OUT
LIQUID IN
VIEW B-B
7/8" TYP.
3 15/16"
3 1/4"
6 3/4"
BOTTOM OF PANEL
Aluminum
Copper
YCAL
Center of Gravity (in.)
YCAL
Center of Gravity (in.)
X
Y
X
Y
0065
59.7
44.9
0065
65.2
44.9
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reli-
able operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable
airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety
cutouts; however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall
– 6'; rear to wall – 6'; cooler end to wall – 4'0"; coil end to wall - 6'; top – no obstructions allowed; distance between adjacent units – 10'.
No more than one adjacent wall may be higher than the unit. 1" nominal deflection isolators (not shown) will increase overall unit height by
6".