Part Load Ratings -

R-22 (English Units)

YCAL0041

% FULL

LOAD

DISPL.

TONS

KW

Ambient

°F

UNIT

EER

100.0

35.0

38.2

95.0

9.6

75.0

28.2

24.5

83.3

11.2

50.0

20.2

14.0

69.7

14.4

25.0

10.6

6.1

55.0

17.0

IPLV: 14.0 EER

YCAL0045

% FULL

LOAD

DISPL.

TONS

KW

Ambient

°F

UNIT

EER

100.0

37.8

41.8

95.0

9.6

73.2

30.3

26.0

83.0

11.5

50.0

22.1

15.5

70.0

14.5

23.2

10.8

6.2

55.0

17.0

IPLV: 14.1 EER

YCAL0051

% FULL

LOAD

DISPL.

TONS

KW

Ambient

°F

UNIT

EER

100.0

43.5

48.7

95.0

9.6

69.2

33.7

28.3

81.4

11.9

48.3

24.4

17.2

68.6

14.6

20.9

13.3

7.2

55.0

18.7

IPLV: 14.4 EER

YCAL0055

% FULL

LOAD

DISPL.

TONS

KW

Ambient

°F

UNIT

EER

100.0

47.6

52.8

95.0

9.6

73.5

37.2

32.3

81.9

11.4

47.0

25.0

17.2

66.5

14.6

23.5

13.0

7.8

55.0

16.3

IPLV: 13.6 EER

YCAL0061

% FULL

LOAD

DISPL.

TONS

KW

Ambient

°F

UNIT

EER

100.0

55.7

62.9

95.0

9.6

69.3

42.4

35.8

80.7

11.9

46.2

30.1

20.4

67.5

15.2

23.1

15.7

9.1

55.0

17.5

IPLV: 14.3 EER

YCAL0065

% FULL

LOAD

DISPL.

TONS

KW

Ambient

°F

UNIT

EER

100.0

60.0

68.3

95.0

9.6

71.5

47.4

40.3

82.4

12.1

50.0

34.7

25.3

69.6

14.5

21.5

16.2

9.0

55.0

18.2

IPLV: 14.5 EER