YORK INTERNATIONAL

7

FORM 150.64-EG1

Options and Accessories

POWER OPTIONS:

COMPRESSOR POWER CONNECTIONS – Single-

point (YCAL0041-0065) terminal block connection(s) are

provided as standard. The following power connections

are available as options. (See electrical data for specific

voltage and options availability.) (

Factory-Mounted.)

SINGLE-POINT SUPPLY TERMINAL BLOCK – (stan-

dard on YCAL0041 - 0065 models). Includes enclosure,

terminal-block and interconnecting wiring to the com-

pressors. Separate external protection must be supplied,

by others, in the incoming compressor-power wiring. (Do

not include this option if either the SinglePoint NonFused

Disconnect Switch or Single-Point Circuit Breaker op-

tions have been included.)

SINGLE-POINT NON-FUSED DISCONNECT SWITCH

Unit-mounted disconnect switch with external, lockable

handle (in compliance with Article 440-14 of N.E.C.),

can be supplied to isolate the unit power voltage for

servicing. Separate external fusing must be supplied,

by others in the power wiring, which must comply with

the National Electrical Code and/or local codes.

SINGLE-POINT CIRCUIT BREAKER – A unit mounted

circuit breaker with external, lockable handle (in com-

pliance with N.E.C. Article 440-14), can be supplied

to isolate the power voltage for servicing. (This option

includes the Single-Point Power connection.)

CONTROL TRANSFORMER – Converts unit power

voltage to 115-1-60 (0.5 or 1.0 KVA capacity). Fac-

tory mounting includes primary and secondary wiring

between the transformer and the control panel. (

Fac-

tory-Mounted.)

POWER FACTOR CORRECTION CAPACITORS – Will

correct unit compressor power factors to a 0.90-0.95.

(

Factory-Mounted.)

CONTROL OPTIONS:

AMBIENT KIT (LOW) – Units will operate to 25°F (-4°C).

This accessory includes all necessary components to

permit chiller operation to 0°F (-18°C). (This option in-

cludes the Discharge Pressure Transducer / Readout

Capability option.) For proper head pressure control in

applications below 25°F (-4°C), where wind gusts may

exceed five mph, it is recommended that Optional Con-

denser Louvered Enclosure Panels also be included.

(

Factory-Mounted.)

AMBIENT KIT (HIGH) – Required if units are to operate

when the ambient temperature is above 115°F (46°C).

Includes discharge pressure transducers. (This option

includes the Discharge Pressure Transducer / Readout-

Capability option.) (

Field-Mounted.)

BUILDING AUTOMATION SYSTEM INTERFACE – The

factory addition of a Printed Circuit Board to accept a

4-20 milliamp, 0-10VDC or contact closure input to reset

the leaving chiller liquid temperature from a Building Au-

tomation System. (Only one of following options can be

offered on a unit at a time: BAS, Remote Control Panel

or Multi-unit Sequence Control.) (

Factory-Mounted.)

(The standard unit capabilities include remote startstop,

remote water temperature reset via a PWM input signal

or up to two steps of demand (load) limiting depending

on model.) (The standard control panel can be directly

connected to a YORK Building Automated System via

the standard onboard RS485 communication port.)

LANGUAGE LCD AND KEYPAD DISPLAY – Spanish,

French, and German unit LCD controls and keypad

display available. Standard language is English.

DISCHARGE PRESSURE TRANSDUCERS AND

READOUT CAPABILITY – The addition of pressure

transducers allows models to sense and display dis-

charge pressure. This is recommended for brine chilling

applications. (This option is included with either the low

or high ambient kits.) (

Factory-Mounted.)

Suction Pressure Transducers: Permits unit to

sense and display suction pressure. This capability

is standard on YCAL0041-0065 models.

MOTOR CURRENT MODULE – Capable of monitoring

compressor motor current. Provides extra protection

against compressor reverse rotation, phase-loss and

phase imbalance. Option consists of one module per

electrical system. (

Factory-Mounted.)

OPTIVIEW REMOTE CONTROL PANEL - Graphical

interface panel to remotely control and monitor up to 8

different units. (Refer to form 201.18-SG4 for detailed

information)

MULTI-UNIT SEQUENCING – A separate Sequencing

Control Center is provided to handle sequencing control

of up to eight chillers in parallel based on mixed liquid

temperature (interconnecting wiring by others). (Only

one of following options can be offered on a unit at a

time: BAS, Remote Control Panel or Multi-unit Sequence

Control.) (

Factory-Mounted.)

COMPRESSOR, PIPING, EVAPORATOR

OPTIONS:

LOW TEMPERATURE BRINE – Required for brine