GENERAL

The 47 - 60 Ton (165 - 210 kW) YCAL models are

shipped complete from the factory ready for installation

and use.

The unit is pressure-tested, evacuated, and fully charged

with Refrigerant-22 (HCFC-22) and includes an initial

oil charge. After assembly, a complete operational test

is performed with water flowing through the cooler to

assure that the refrigeration circuit operates correctly.

The unit structure is heavy-gauge, galvanized steel. This

galvanized steel is coated with baked-on powder paint,

which, when subjected to ASTM B117 1000 hour, salt

spray testing, yields a minimum ASTM 1654 rating of

“6”. Corrosion resistant wire mesh panels are added to

protect the condenser coil from incidental damage and

restrict unauthorized access to internal components.

Units are designed in accordance with NFPA 70 (Na-

tional Electric Code), ASHRAE/ANSI 15 Safety code for

mechanical refrigeration, ASME, Listed and labeled with

Intertek Testing Services (ETL) and rated in accordance

with ARI Standard 550/590-2003.

COMPRESSORS

The chiller has suction-gas cooled, hermetic, scroll com-

pressors. The YCAL compressors incorporate a compli-

ant scroll design in both the axial and radial direction. All

rotating parts are statically and dynamically balanced. A

large internal volume and oil reservoir provides greater

liquid tolerance. Compressor crankcase heaters are also

included for extra protection against liquid migration.

COOLER

The cooler is equipped with a heater controlled by a

separate thermostat. The heater provides freeze protec-

tion for the cooler down to -20°F (-29°C) ambient. The

cooler is covered with 3/4” (19mm) flexible, closed-cell,

foam insulation (K~0.25).

Brazed plate heat exchangers shall be UL (Underwriters

Laboratories) listed. Installing contractor must include

accommodations in the chilled water piping to allow

proper drainage and venting of the heat exchanger.

Water inlet and outlet connections are grooved for com-

patibility with factory supplied victaulic connections.

A strainer with a mesh size between .5 and 1.5 mm (40

mesh) is recommended upstream of the heat exchanger

to prevent clogging.

CONDENSER

Coils – Fin and tube condenser coils of seamless, inter-

nally-enhanced, high-condensing-coefficient, corrosion

resistant copper tubes are arranged in staggered rows,

mechanically expanded into aluminum fins. Integral

subcooling is included. The design working pressure of

the coil is 450 PSIG (31 bar).

Low Sound Fans – The condenser fans are composed

of corrosion resistant aluminum hub and glass-fiberrein-

forced composite blades molded into a low noise airfoil

section. They are designed for maximum efficiency and

are statically and dynamically balanced for vibration free

operation. They are directly driven by independent mo-

tors, and positioned for vertical air discharge. All blades

are statically and dynamically balanced for vibration-free

operation. The fan guards are constructed of heavy-

gauge, rust-resistant, PVCcoated steel wire.

Motors – The fan motors are Totally Enclosed Air-Over,

squirrel-cage type, current protected. They feature

ball bearings that are double-sealed and permanently

lubricated.