53 electrical data 40 ton with power, Exhaust r22 – York Y33 User Manual
Page 68
246653-YTG-E-0108
68
Johnson Controls Unitary Products
TABLE 53: ELECTRICAL DATA 40 TON WITH POWER EXHAUST R22
V
OLTAGE
C
OMPRESSORS
(
EACH
)
OD F
AN
M
OTORS
(
EACH
)
S
UPPLY
B
LOWER
P
WR
E
XH
M
OTOR
MCA
1
(A
MPS
)
M
AX
F
USE
2
/
B
REAKER
3
S
IZE
Q
TY
.
RLA
LRA
MCC
Q
TY
FLA
HP
FLA
HP
FLA
208-3-60
4
37.2
239
58.0
4
4.5
10
30.8
7.5
24.2
231
250
10
30.8
238
250
15
46.2
255
300
15
46.2
7.5
24.2
249
250
10
30.8
255
300
15
46.2
271
300
20
59.4
7.5
24.2
265
300
10
30.8
272
300
15
46.2
287
300
25
74.8
7.5
24.2
285
350
10
30.8
291
350
15
46.2
307
350
230-3-60
4
37.2
239
58.0
4
4.5
10
28.0
7.5
22.0
225
250
10
28.0
231
250
15
42.0
247
250
15
42.0
7.5
22.0
241
250
10
28.0
247
250
15
42.0
261
300
20
54.0
7.5
22.0
256
300
10
28.0
262
300
15
42.0
276
300
25
68.0
7.5
22.0
273
300
10
28.0
279
300
15
42.0
293
350
460-3-60
4
17.2
125
27.0
4
2.2
10
14.0
7.5
11.0
107
110
10
14.0
110
125
15
21.0
118
125
15
21.0
7.5
11.0
115
125
10
14.0
118
125
15
21.0
125
125
20
27.0
7.5
11.0
122
125
10
14.0
125
150
15
21.0
132
150
25
34.0
7.5
11.0
131
150
10
14.0
134
150
15
21.0
141
150
575-3-60
4
12.4
80
19.3
4
1.7
10
11.0
7.5
9.0
80
90
10
11.0
82
90
15
17.0
89
100
15
17.0
7.5
9.0
87
100
10
11.0
89
100
15
17.0
95
110
20
22.0
7.5
9.0
93
110
10
11.0
95
110
15
17.0
101
110
25
27.0
7.5
9.0
99
125
10
11.0
101
125
15
17.0
107
125
1.
Minimum Circuit Ampacity.
2.
Dual Element, Time Delay Type.
3.
HACR type per NEC