52 electrical data 30 ton with power, Exhaust r22 – York Y33 User Manual
Page 67
246653-YTG-E-0108
Johnson Controls Unitary Products
67
TABLE 52: ELECTRICAL DATA 30 TON WITH POWER EXHAUST R22
V
OLTAGE
C
OMPRESSORS
(
EACH
)
OD F
AN
M
OTORS
(
EACH
)
S
UPPLY
B
LOWER
P
WR
E
XH
M
OTOR
MCA
1
(A
MPS
)
M
AX
F
USE
2
/
B
REAKER
3
S
IZE
Q
TY
.
RLA
LRA
MCC
Q
TY
FLA
HP
FLA
HP
FLA
208-3-60
3
37.2
239
58.0
3
4.5
10
30.8
7.5
24.2
189
225
10
30.8
196
225
15
46.2
214
250
15
46.2
7.5
24.2
207
250
10
30.8
214
250
15
46.2
229
250
20
59.4
7.5
24.2
224
250
10
30.8
230
250
15
46.2
246
300
25
74.8
7.5
24.2
243
300
10
30.8
249
300
15
46.2
265
300
230-3-60
3
37.2
239
58.0
3
4.5
10
28.0
7.5
22.0
184
200
10
28.0
190
225
15
42.0
205
225
15
42.0
7.5
22.0
199
225
10
28.0
205
225
15
42.0
219
250
20
54.0
7.5
22.0
214
250
10
28.0
220
250
15
42.0
234
250
25
68.0
7.5
22.0
232
250
10
28.0
238
300
15
42.0
252
300
460-3-60
3
17.2
125
27.0
3
2.2
10
14.0
7.5
11.0
87
100
10
14.0
90
100
15
21.0
98
110
15
21.0
7.5
11.0
95
110
10
14.0
98
110
15
21.0
105
125
20
27.0
7.5
11.0
103
125
10
14.0
106
125
15
21.0
113
125
25
34.0
7.5
11.0
112
125
10
14.0
115
125
15
21.0
122
150
575-3-60
3
12.4
80
19.3
3
1.7
10
11.0
7.5
9.0
65
70
10
11.0
67
70
15
17.0
75
90
15
17.0
7.5
9.0
73
80
10
11.0
75
90
15
17.0
81
90
20
22.0
7.5
9.0
79
100
10
11.0
81
100
15
17.0
87
100
25
27.0
7.5
9.0
85
110
10
11.0
87
110
15
17.0
93
110
1.
Minimum Circuit Ampacity.
2.
Dual Element, Time Delay Type.
3.
HACR type per NEC