background image

246653-YTG-E-0108

Johnson Controls Unitary Products

53

4. Shaded RPMs require Class II blower.

A

IRFLOW

(CFM)

A

VAILABLE

E

XTERNAL

S

TATIC

P

RESSURE

(IWG)

4.2

4.4

4.6

4.8

5.0

RPM

BHP

3

RPM

BHP

3

RPM

BHP

3

RPM

BHP

3

RPM

BHP

3

4000

1601

4.6

1636

4.9

1672

5.2

1707

5.5

1740

5.8

5000

1621

5.3

1656

5.6

1691

5.9

1725

6.2

1758

6.5

6000

1653

6.1

1687

6.4

1720

6.7

1753

7.0

1785

7.4

7000

1698

7.0

1730

7.3

1761

7.7

1792

8.0

1822

8.4

8000

1754

8.0

1784

8.4

1814

8.8

1843

9.1

1872

9.5

9000

1822

9.3

1850

9.7

1877

10.0

1905

10.4

1932

10.8

10000

1898

10.7

1924

11.1

1950

11.5

1976

11.9

2001

12.3

11000

1982

12.3

2006

12.7

2030

13.1

2054

13.6

2078

14.0

12000

2072

14.1

2095

14.6

2117

15.0

2140

15.5

2162

15.9

13000

2167

16.2

2188

16.7

2210

17.2

2231

17.7

2252

18.2

14000

2265

18.6

2286

19.1

2306

19.6

2326

20.1

2346

20.6

15000

2368

21.1

2387

21.7

2406

22.2

2425

22.8

2444

23.3

A

IRFLOW

(CFM)

A

VAILABLE

E

XTERNAL

S

TATIC

P

RESSURE

(IWG)

5.2

5.4

5.6

5.8

6.0

RPM

BHP

3

RPM

BHP

3

RPM

BHP

3

RPM

BHP

3

RPM

BHP

3

4000

1774

6.1

1807

6.4

1838

6.7

1870

7.0

1902

7.3

5000

1791

6.8

1823

7.1

1855

7.5

1886

7.8

1917

8.1

6000

1817

7.7

1847

8.0

1878

8.4

1909

8.7

1938

9.1

7000

1853

8.7

1883

9.1

1912

9.4

1941

9.8

1970

10.2

8000

1901

9.9

1928

10.2

1956

10.6

1984

11.0

2012

11.4

9000

1958

11.2

1985

11.6

2012

12.0

2038

12.4

2064

12.8

10000

2026

12.7

2051

13.1

2076

13.6

2101

14.0

2125

14.4

11000

2102

14.5

2126

14.9

2149

15.3

2172

15.8

2196

16.3

12000

2185

16.4

2207

16.9

2229

17.4

2251

17.9

2273

18.3

13000

2273

18.6

2294

19.1

2315

19.6

2336

20.1

2356

20.6

14000

2366

21.1

2386

21.6

2406

22.1

2425

22.6

2445

23.2

15000

2463

23.8

2482

24.4

2501

24.9

1.

Fan performance is based on wet evaporator coils, clean 2” throwaway filters and system/cabinet effects at standard air density and 0 feet elevation.

2.

Refer to Tables 10, 12, 15, 18, 21, 23 and 42 for component additions and deductions to fan performance tables.

3.

BHP includes drive losses.

TABLE 40: FAN PERFORMANCE - 25 & 30 TON AIRFOIL

1,2

(CONTINUED)

This manual is related to the following products: