Continued) – York Y33 User Manual
Page 53
246653-YTG-E-0108
Johnson Controls Unitary Products
53
4. Shaded RPMs require Class II blower.
A
IRFLOW
(CFM)
A
VAILABLE
E
XTERNAL
S
TATIC
P
RESSURE
(IWG)
4.2
4.4
4.6
4.8
5.0
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
4000
1601
4.6
1636
4.9
1672
5.2
1707
5.5
1740
5.8
5000
1621
5.3
1656
5.6
1691
5.9
1725
6.2
1758
6.5
6000
1653
6.1
1687
6.4
1720
6.7
1753
7.0
1785
7.4
7000
1698
7.0
1730
7.3
1761
7.7
1792
8.0
1822
8.4
8000
1754
8.0
1784
8.4
1814
8.8
1843
9.1
1872
9.5
9000
1822
9.3
1850
9.7
1877
10.0
1905
10.4
1932
10.8
10000
1898
10.7
1924
11.1
1950
11.5
1976
11.9
2001
12.3
11000
1982
12.3
2006
12.7
2030
13.1
2054
13.6
2078
14.0
12000
2072
14.1
2095
14.6
2117
15.0
2140
15.5
2162
15.9
13000
2167
16.2
2188
16.7
2210
17.2
2231
17.7
2252
18.2
14000
2265
18.6
2286
19.1
2306
19.6
2326
20.1
2346
20.6
15000
2368
21.1
2387
21.7
2406
22.2
2425
22.8
2444
23.3
A
IRFLOW
(CFM)
A
VAILABLE
E
XTERNAL
S
TATIC
P
RESSURE
(IWG)
5.2
5.4
5.6
5.8
6.0
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
4000
1774
6.1
1807
6.4
1838
6.7
1870
7.0
1902
7.3
5000
1791
6.8
1823
7.1
1855
7.5
1886
7.8
1917
8.1
6000
1817
7.7
1847
8.0
1878
8.4
1909
8.7
1938
9.1
7000
1853
8.7
1883
9.1
1912
9.4
1941
9.8
1970
10.2
8000
1901
9.9
1928
10.2
1956
10.6
1984
11.0
2012
11.4
9000
1958
11.2
1985
11.6
2012
12.0
2038
12.4
2064
12.8
10000
2026
12.7
2051
13.1
2076
13.6
2101
14.0
2125
14.4
11000
2102
14.5
2126
14.9
2149
15.3
2172
15.8
2196
16.3
12000
2185
16.4
2207
16.9
2229
17.4
2251
17.9
2273
18.3
13000
2273
18.6
2294
19.1
2315
19.6
2336
20.1
2356
20.6
14000
2366
21.1
2386
21.6
2406
22.1
2425
22.6
2445
23.2
15000
2463
23.8
2482
24.4
2501
24.9
1.
Fan performance is based on wet evaporator coils, clean 2” throwaway filters and system/cabinet effects at standard air density and 0 feet elevation.
2.
Refer to Tables 10, 12, 15, 18, 21, 23 and 42 for component additions and deductions to fan performance tables.
3.
BHP includes drive losses.
TABLE 40: FAN PERFORMANCE - 25 & 30 TON AIRFOIL
1,2
(CONTINUED)