beautypg.com

Zh037-150 bottom duct application – York PREDATOR R-410A User Manual

Page 64

background image

528150-YTG-C-1109

64

Johnson Controls Unitary Products

ZH037-150 Bottom Duct Application

ZH037 (3.0 Ton) Bottom Duct

Air Flow

(CFM)

Available External Static Pressure - IWG

1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

Standard 1.5 HP & Drive

Hi Static 1.5 HP & Drive

900

605

0.23

671

0.33

738

0.42

804

0.52

869

0.62

933

0.71

995

0.80

1054

0.89

1111

0.98

1164

1.07

1000

621

0.25

688

0.34

754

0.44

820

0.53

885

0.63

949

0.72

1011

0.82

1071

0.91

1127

1.00

1180

1.09

1100

637

0.27

703

0.36

769

0.46

835

0.56

900

0.65

964

0.74

1026

0.84

1086

0.93

1142

1.02

1195

1.11

1200

651

0.30

717

0.39

784

0.49

850

0.58

915

0.68

979

0.77

1041

0.87

1100

0.96

1157

1.05

1210

1.13

1300

666

0.33

732

0.43

799

0.52

865

0.62

930

0.71

994

0.81

1056

0.90

1115

0.99

1172

1.08

1225

1.17

1400

681

0.37

747

0.47

814

0.56

880

0.66

945

0.75

1009

0.85

1071

0.94

1130

1.03

1187

1.12

1240

1.21

1500

697

0.42

763

0.51

830

0.61

896

0.71

961

0.80

1025

0.90

1087

0.99

1146

1.08

1203

1.17

1256

1.26

1.5 HP & Field Supplied Drive

ZH049 (4.0 Ton) Bottom Duct

Air Flow

(CFM)

Available External Static Pressure - IWG

1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
4. Field Supplied Drive.

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

FS

4

Standard 1.5 HP & Drive

Hi Static 1.5 HP & Drive

1200

651

0.30

717

0.39

784

0.49

850

0.58

915

0.68

979

0.77

1041

0.87

1100

0.96

1157

1.05

1210

1.13

1300

666

0.33

732

0.43

799

0.52

865

0.62

930

0.71

994

0.81

1056

0.90

1115

0.99

1172

1.08

1225

1.17

1400

681

0.37

747

0.47

814

0.56

880

0.66

945

0.75

1009

0.85

1071

0.94

1130

1.03

1187

1.12

1240

1.21

1500

697

0.42

763

0.51

830

0.61

896

0.71

961

0.80

1025

0.90

1087

0.99

1146

1.08

1203

1.17

1256

1.26

1600

714

0.47

780

0.57

846

0.66

913

0.76

978

0.86

1042

0.95

1103

1.04

1163

1.14

1220

1.22

1273

1.31

1700

732

0.53

798

0.63

864

0.73

930

0.82

996

0.92

1059

1.01

1121

1.10

1181

1.20

1237

1.29

1291

1.37

1800

751

0.60

817

0.70

883

0.79

950

0.89

1015

0.98

1079

1.08

1140

1.17

1200

1.26

1257

1.35

1310

1.44

1900

771

0.68

837

0.77

904

0.87

970

0.96

1035

1.06

1099

1.15

1161

1.25

1220

1.34

1277

1.43

-

-

2000

793

0.75

859

0.85

925

0.95

991

1.04

1056

1.14

1120

1.23

1182

1.32

1242

1.42

1298

1.51

-

-

ZH061 (5.0 Ton) Bottom Duct

Air Flow

(CFM)

Available External Static Pressure - IWG

1

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

1.5 HP & Field Supplied Drive

Standard 1.5 HP & Drive

Hi Static 2 HP & Drive

1500

673

0.47

736

0.54

797

0.63

855

0.72

910

0.82

964

0.92

1016

1.03

1067

1.14

1117

1.25

1166

1.36

1600

693

0.49

756

0.57

817

0.65

874

0.75

930

0.85

984

0.95

1036

1.06

1087

1.17

1137

1.28

1186

1.39

1700

713

0.53

777

0.60

837

0.69

895

0.78

951

0.88

1004

0.98

1057

1.09

1107

1.20

1157

1.31

1207

1.42

1800

734

0.57

797

0.65

858

0.73

916

0.83

971

0.92

1025

1.03

1077

1.14

1128

1.25

1178

1.36

1228

1.47

1900

755

0.62

819

0.70

879

0.79

937

0.88

992

0.98

1046

1.08

1098

1.19

1149

1.30

1199

1.41

1249

1.52

2000

776

0.69

840

0.76

900

0.85

958

0.94

1014

1.04

1067

1.14

1120

1.25

1171

1.36

1221

1.47

1270

1.59

2100

798

0.76

861

0.84

921

0.92

979

1.02

1035

1.11

1089

1.22

1141

1.32

1192

1.44

1242

1.55

1291

1.66

2200

819

0.84

882

0.92

943

1.00

1001

1.10

1056

1.20

1110

1.30

1162

1.41

1213

1.52

1263

1.63

1312

1.74

2300

840

0.93

903

1.01

964

1.10

1022

1.19

1077

1.29

1131

1.39

1183

1.50

1234

1.61

1284

1.72

1334

1.83

2400

861

1.03

925

1.11

985

1.20

1043

1.29

1099

1.39

1152

1.49

1204

1.60

1255

1.71

1305

1.82

1355

1.93

2500

882

1.14

946

1.22

1006

1.30

1064

1.40

1120

1.50

1173

1.60

1226

1.71

1276

1.82

1326

1.93

1376

2.04

3 HP & Field Supplied Drive