beautypg.com

York PREDATOR R-410A User Manual

Page 54

background image

528150-YTG-C-1109

54

Johnson Controls Unitary Products

115°F

125°F

1875

77

90.4

8.3

33.6

30.2

21.8

-

-

-

81.7

8.9

32.0

25.5

18.7

-

-

-

72

81.1

8.0

51.6

43.1

34.6

26.2

-

-

72.9

8.6

48.1

39.7

31.4

23.0

-

-

67

71.9

7.8

69.5

56.0

47.5

39.0

30.6

-

64.1

8.3

64.1

52.4

44.0

35.7

27.3

-

62

63.9

7.6

63.9

63.9

59.0

50.5

42.0

33.6

57.3

8.1

57.3

57.3

57.3

46.5

38.2

29.8

2250

77

92.7

8.3

43.8

33.9

24.0

-

-

-

83.2

9.0

43.2

30.5

20.7

-

-

-

72

83.2

8.1

58.0

48.1

38.2

28.3

-

-

74.3

8.7

54.3

44.5

34.8

25.0

-

-

67

73.7

7.9

72.2

62.3

52.4

42.5

32.6

-

65.3

8.4

65.3

58.5

48.8

39.0

29.3

-

62

65.6

7.7

65.6

65.6

65.1

55.2

45.3

35.4

58.4

8.2

58.4

58.4

58.4

51.1

41.3

31.6

57

68.8

7.7

68.8

68.8

61.5

51.6

41.7

31.8

62.7

8.3

62.7

62.7

56.0

46.3

36.5

26.8

2625

77

95.1

8.4

53.9

37.5

26.3

-

-

-

84.8

9.1

54.4

35.5

22.8

-

-

-

72

85.4

8.2

64.4

53.1

41.8

30.5

-

-

75.7

8.8

60.5

49.3

38.2

27.0

-

-

67

75.6

7.9

74.8

68.6

57.3

46.0

34.7

-

66.5

8.5

66.5

64.7

53.5

42.4

31.2

-

62

67.2

7.7

67.2

67.2

71.2

59.9

48.6

37.3

59.5

8.2

59.5

59.5

59.5

55.6

44.5

33.3

57

70.6

7.8

70.6

70.6

67.2

55.9

44.6

33.3

63.9

8.4

63.9

63.9

61.5

50.4

39.2

28.0

3000

77

97.5

8.5

64.0

41.2

28.5

-

-

-

86.4

9.1

65.7

40.5

24.8

-

-

-

72

87.5

8.2

70.8

58.1

45.4

32.6

-

-

77.1

8.8

66.7

54.1

41.6

29.0

-

-

67

77.5

8.0

77.5

74.9

62.2

49.5

36.8

-

67.8

8.6

67.8

67.8

58.3

45.8

33.2

-

62

68.9

7.8

68.9

68.9

77.2

64.5

51.8

39.1

60.6

8.3

60.6

60.6

60.6

60.2

47.6

35.0

57

72.3

7.9

72.3

72.3

73.0

60.3

47.6

34.8

65.1

8.4

65.1

65.1

65.1

54.4

41.9

29.3

3375

72

88.7

8.3

77.5

63.3

49.1

34.8

-

-

77.7

8.9

73.3

59.2

45.1

31.0

-

-

67

78.6

8.0

78.6

77.3

67.3

53.1

38.8

-

68.3

8.6

68.3

68.3

63.3

49.2

35.1

-

62

69.9

7.8

69.9

69.9

74.1

59.8

45.6

31.4

61.1

8.4

61.1

61.1

61.1

53.1

39.0

24.9

57

73.4

7.9

73.4

73.4

73.7

59.5

45.2

31.0

65.7

8.5

65.7

65.7

65.7

52.5

38.4

24.3

3750

72

90.0

8.3

84.3

68.5

52.8

37.0

-

-

78.4

8.9

78.4

64.3

48.6

33.0

-

-

67

79.7

8.1

79.7

79.7

72.4

56.6

40.9

-

68.9

8.6

68.9

68.9

68.2

52.6

37.0

-

62

70.9

7.9

70.9

70.9

70.9

55.1

39.4

23.6

61.6

8.4

61.6

61.6

61.6

46.0

30.4

14.8

57

74.4

7.9

74.4

74.4

74.4

58.7

42.9

27.2

66.3

8.5

66.3

66.3

66.3

50.6

35.0

19.4

1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower

Performance Table for the kW of the supply air blower motor.

2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

ZJ090 (7.5 Ton) (Continued)

Air on

Evaporator Coil

Temperature of Air on Condenser Coil

Total

Capacity

1

(MBh)

Total
Input

(kW)

2

Sensible Capacity (MBh)

Total

Capacity

1

(MBh)

Total
Input

(kW)

2

Sensible Capacity (MBh)

CFM

WB
(°F)

Return Dry Bulb (°F)

Return Dry Bulb (°F)

90

85

80

75

70

65

90

85

80

75

70

65