York PREDATOR R-410A User Manual
Page 58

528150-YTG-C-1109
58
Johnson Controls Unitary Products
115°F
125°F
2500
77
113.0
11.0
47.0
40.7
30.0
-
-
-
101.1
12.1
44.1
37.0
26.4
-
-
-
72
104.5
11.0
69.2
58.5
47.8
37.1
-
-
93.6
12.1
65.1
54.5
43.9
33.3
-
-
67
96.0
11.0
91.4
76.3
65.6
55.0
44.3
-
86.1
12.1
86.1
72.0
61.4
50.8
40.2
-
62
89.7
11.0
89.7
89.7
79.8
69.1
58.4
47.7
81.3
12.1
81.3
81.3
74.1
63.0
52.3
41.7
3000
77
119.6
11.1
58.6
46.1
33.6
-
-
-
108.1
12.1
57.2
42.5
30.0
-
-
-
72
110.6
11.1
78.6
66.1
53.5
41.0
-
-
100.1
12.2
74.7
62.2
49.8
37.3
-
-
67
101.6
11.1
98.5
86.0
73.5
61.0
48.5
-
92.1
12.2
92.1
82.0
69.5
57.1
44.6
-
62
94.9
11.0
94.9
94.9
89.3
76.8
64.3
51.8
87.0
12.2
87.0
87.0
83.3
70.9
58.4
46.0
57
94.9
11.0
94.9
94.9
85.5
73.0
60.5
47.9
86.7
12.0
86.7
86.7
77.8
65.3
52.9
40.4
3500
77
126.1
11.2
70.2
51.5
37.2
-
-
-
115.1
12.2
70.3
47.9
33.6
-
-
-
72
116.6
11.2
87.9
73.6
59.3
44.9
-
-
106.6
12.3
84.2
69.9
55.6
41.3
-
-
67
107.2
11.2
105.6
95.7
81.4
67.0
52.7
-
98.1
12.3
98.1
92.0
77.7
63.4
49.1
-
62
100.1
11.1
100.1
100.1
98.9
84.6
70.2
55.9
92.6
12.3
92.6
92.6
92.6
78.8
64.6
50.3
57
100.1
11.0
100.1
100.1
94.6
80.3
66.0
51.6
92.3
12.1
92.3
92.3
87.0
72.7
58.4
44.1
4000
77
132.7
11.3
81.8
56.9
40.8
-
-
-
122.2
12.3
83.4
53.3
37.1
-
-
-
72
122.7
11.3
97.3
81.1
65.0
48.8
-
-
113.1
12.4
93.7
77.6
61.5
45.3
-
-
67
112.7
11.3
112.7
105.4
89.2
73.1
56.9
-
104.1
12.4
104.1
102.0
85.8
69.7
53.6
-
62
105.3
11.2
105.3
105.3
108.4
92.3
76.1
60.0
98.2
12.4
98.2
98.2
98.2
86.8
70.7
54.5
57
105.3
11.1
105.3
105.3
103.7
87.6
71.5
55.3
98.0
12.2
98.0
98.0
96.2
80.0
63.9
47.8
4500
72
123.4
11.2
104.9
87.3
69.6
52.0
-
-
113.1
12.3
100.8
83.3
65.8
48.3
-
-
67
113.3
11.2
113.3
109.7
95.6
78.0
60.4
-
104.1
12.3
104.1
104.0
91.9
74.4
56.9
-
62
105.9
11.2
105.9
105.9
107.5
89.8
72.2
54.6
98.2
12.3
98.2
98.2
98.2
83.1
65.6
48.1
57
105.9
11.1
105.9
105.9
105.1
87.5
69.9
52.2
98.0
12.2
98.0
98.0
97.1
79.6
62.1
44.6
5000
72
124.0
11.2
112.5
93.4
74.3
55.2
-
-
113.1
12.3
107.8
89.0
70.1
51.3
-
-
67
113.9
11.2
113.9
113.9
102.0
82.9
63.8
-
104.1
12.3
104.1
104.1
97.9
79.1
60.3
-
62
106.5
11.2
106.5
106.5
106.5
87.4
68.3
49.2
98.2
12.3
98.2
98.2
98.2
79.4
60.6
41.7
57
106.4
11.1
106.4
106.4
106.4
87.3
68.3
49.2
98.0
12.1
98.0
98.0
98.0
79.1
60.3
41.5
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZJ120 (10 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F)
Return Dry Bulb (°F)
90
85
80
75
70
65
90
85
80
75
70
65