11.3

11.3

11.3

11.3 Inverter Fault Codes

Inverter Fault Codes

Inverter Fault Codes

Inverter Fault Codes

LCD Display Message

Data

(Hex)

Explanation

NO ERROR

××

00

No error has been recorded since the last inverter reset or trip clear

OVERCURRENT (ACCEL)

(PRESS CLEAR)

××

01

Overcurrent during acceleration

OVERCURRENT (DECEL)

(PRESS CLEAR)

××

02

Overcurrent during deceleration

OVERCURRENT (RUN)

(PRESS CLEAR)

××

03

Overcurrent during constant-speed run

LOAD-END OVERCURRENT

(PRESS CLEAR)

××

04

Load-end overcurrent detected at start-up (output terminals, motor
wiring etc.)

U-PHASE SHORT CKT

(PRESS CLEAR)

××

05

U-phase armature short circuit

V-PHASE SHORT CKT

(PRESS CLEAR)

××

06

V-phase armature short circuit

W-PHASE SHORT CKT

(PRESS CLEAR)

××

07

W-phase armature short circuit

LOST INPUT PHASE

(PRESS CLEAR)

××

08

Lost input phase (option)

LOST OUTPUT PHASE

(PRESS CLEAR)

××

09

Lost output phase (option)

OVERVOLTAGE (ACCEL)

(PRESS CLEAR)

××

0A

Overvoltage during acceleration

OVERVOLTAGE (DECEL)

(PRESS CLEAR)

××

0B

Overvoltage during deceleration

OVERVOLTAGE (RUN)

(PRESS CLEAR)

××

0C

Overvoltage during constant-speed run

INVERTER OVERLOAD

(PRESS CLEAR)

××

0D

Inverter overload

MOTOR OVERLOAD

(PRESS CLEAR)

××

0E

Motor overload

DBR OVERLOAD TRIP

(PRESS CLEAR)

××

0F

Dynamic braking resistor overload

OVERHEAT TRIP

(PRESS CLEAR)

××

10

Inverter overheat

EMERGENCY OFF

(PRESS CLEAR)

××

11

Emergency off

EEPROM WRITE FAILURE

(PRESS CLEAR)

××

12

EEPROM failure during write

EEPROM READ FAILURE

(PRESS CLEAR)

××

13

EEPROM failure during initial read

××

14

Unused

RAM ERROR

(PRESS CLEAR)

××

15

RAM error

ROM ERROR

(PRESS CLEAR)

××

16

ROM error

CPU ERROR

(PRESS CLEAR)

××

17

CPU error

COMMUNICATION ERROR

(PRESS CLEAR)

××

18

RS232C timer time-out

GATE ARRAY FAULT

(PRESS CLEAR)

××

19

Gate array error