Read-only registers – Toshiba G3 TOSVERT-130 User Manual
Page 32
31
11.1
11.1
11.1
11.1 Read
Read
Read
Read----Only Registers
Only Registers
Only Registers
Only Registers
Register Bit
Function
Bank Mask
Adjustment
Range
Multiplier
01
∼
09
word Reserved
0A
word
RX terminal analog input
value
0
FFFF
0000 ~ 7FFF (-100% ~ 0%)
7FFF ~ FFFF (0% ~ 100%)
1
0B word
Frequency
command
monitor
0 FFFF
0000
∼
9C40
(0.00
∼
400.00 Hz)
0.01
0C word
Input voltage monitor(Note 1)
0
FFFF
0 ~ 255%
0.1
0D word
Output
terminal
status
monitor
0
00FF
Refer to Table 4 (page 32)
0E
word
Inverter Status 1
0
FFFF
Refer to Table 5 (page 32)
0F
word
Inverter Status 2
0
00FF
Refer to Table 6 (page 32)
10 word
Present
trip
0 00FF
11 high
byte
4th Past trip (most recent)
0
7F00
low
byte
3rd past trip
007F
Refer to section 11.3 for fault
codes
12 high
byte
2nd past trip
0
7F00
low
byte
1st past trip (oldest)
007F
13 word
Pre-compensation
output
frequency
0 FFFF
0000
∼
9C40
(0.00
∼
400.00 Hz)
0.01
14 word
Post-compensation
output
frequency
0 FFFF
0000
∼
9C40
(0.00
∼
400.00 Hz)
0.01
15 word
Torque
current
monitor
0 FFFF
(Note 2)
0.01
16 word
Excitation
current
monitor
0 00FF
00
∼
FF (0 ~ 255%)
1
17 word
PID
feedback
value
0 FFFF
(Note 2)
0.02
18
word
Motor overload ratio
0
FFFF
0 ~ 65535
100/65535
19
word
Inverter overload ratio
0
FFFF
0 ~ 65535
100/65535
1A
word
DBR overload ratio
0
FFFF
0 ~ 65535
100/65535
1B
word
Input power (%)
0
FFFF
0 ~ 6553.5
0.1
1C
word
Input power (kW)
0
FFFF
(Note 3)
1D
word
Output power (%)
0
FFFF
(Note 2)
0.1
1E
word
Output power (kW)
0
FFFF
(Note 2, Note 3)
1F, 20
word
Reserved
21
word
Input / output power units
0
0008
0000: 0.01kW
0008: 0.1kW
22
word
Command mode status
0
0003
0000: terminal
0001: panel
0002: option
0003: RS232C
23 word
Frequency
mode
selection
status
0 000C
0000:
terminal
0004: panel
0008: option
000C: RS232C
24 low
byte
Profibus interface card
software revision
high
byte
Profibus interface card
software version
25
word
Output current (amps)
FFFF
0.0 ~ 6553.5 A
0.1
(Note 1)
These monitor voltage units are not affected by the setting of
VOLTAGE UNITS SELECTION
in
GROUP:UTILITY PARAMETERS
; they are always in units of %.
(Note 2)
These registers use signed data (data values larger than 7FFF
H
are negative). If the register data is
8000
H
or larger, the actual value can be obtained by: actual value = - [FFFF
H
- (register data) + 1].