Group:communication setting parameters – Toshiba G3 TOSVERT-130 User Manual
Page 50
49
11.2.10
11.2.10
11.2.10
11.2.10 GROUP:COMMUNICATION SETTING PARAMETERS
GROUP:COMMUNICATION SETTING PARAMETERS
GROUP:COMMUNICATION SETTING PARAMETERS
GROUP:COMMUNICATION SETTING PARAMETERS
Register
Function / Title
Bank
Mask
Adjustment Range
Multiplier
1D0
∼
200
Reserved
201
RS232 BAUD RATE
1
0018
0000: 2400 baud
(0)
0008: 4800 baud
(1)
0010: 9600 baud
(2)
202
NUMBER OF DATA BITS
1 0040
0000:
7
bits
(0)
0040: 8 bits
(1)
.203
PARITY SETTING
1
0080
0000: Even parity
(0)
0080: Odd parity
(1)
204
INVERTER ID NUMBER
1 00FF
0000
∼
00FF (0
∼
255) Note 1
1
205
COMMUNICATION
SELECTION
1 0007
0000:
OFF
(0)
0001: RS485
(1)
0002: Profibus, Modbus, DNet
(2)
0003: TOSLINE S-20
(3)
0004: 12 bit binary input
(4)
0005: 3-digit BCD (0.1Hz)
(5)
0006: 3-digit BCD (1Hz)
(6)
206 1
MASTER/SLAVE
SELECTION
1 0018
0000:
Slave
(0)
0008: Master (frequency command)
(1)
0010: Master (output frequency) (2)
207
RS485 BAUD RATE
1
0004
0000: Normal mode
(0)
0004: High-speed mode
(1)
208 2
TOSLINE-F10
COMMAND INPUT
1 0003
0000:
OFF
(0)
0001: Frequency command
(1)
0002: Command input
(2)
0003: Both (1) and (2)
(3)
209
TOSLINE-F10
MONITOR OUTPUT
1 003C
0000:
(0) 0020:
(8)
0004: (1)
0024: (9)
0008: (2)
0028: (10)
000C: (3)
002C: (11)
0010: (4)
0030: (12)
0014: (5)
0034: (13)
0018: (6)
0038: (14)
001C: (7)
003C: (15
)
20A
TOSLINE-F10 COMM
ERROR MODE
1
0080
0000: Data cleared
(0)
0080: Data retained
(1)
20B 3
TOSLINE-S20
RECEIVE ADDRESS
1 FFFF
0000
∼
03FF (0
∼
1023)
1
20C
TOSLINE-S20
TRANSMIT ADDRESS
1 FFFF
0000
∼
03FF (0
∼
1023)
1
20D
TOSLINE-S20
COMMAND INPUT
1 001F
0000
∼
001F (0
∼
31)
1
20E
TOSLINE-S20
MONITOR OUTPUT
1 001F
0000
∼
001F (0
∼
31)
1
20F
TOSLINE-S20 FREQ
REF ADDR SELECT
1 0001
0000:
Disable
(0)
0001: Enable
(1)
1
210
1
TOSLINE-S20
FREQ REFERENCE
ADDR
1 FFFF
0000
∼
03FF (0
∼
1023)
1
Note 1: Although the
INVERTER ID NUMBER
parameter can be set from 0 to 255, the allowable Profibus slave
addresses range only from 0 to 125. Therefore, if this parameter is set to a value from 126 to 255, the
Profibus interface card will trip “OPTION PCB ERROR” upon initialization.