11.2.10 GROUP:COMMUNICATION SETTING PARAMETERS

GROUP:COMMUNICATION SETTING PARAMETERS

GROUP:COMMUNICATION SETTING PARAMETERS

GROUP:COMMUNICATION SETTING PARAMETERS

Register

Function / Title

Bank

Mask

Adjustment Range

Multiplier

1D0

200

Reserved

201

RS232 BAUD RATE

1

0018

0000: 2400 baud

(0)

0008: 4800 baud

(1)

0010: 9600 baud

(2)

202

NUMBER OF DATA BITS

1 0040

0000:

7

bits

(0)

0040: 8 bits

(1)

.203

PARITY SETTING

1

0080

0000: Even parity

(0)

0080: Odd parity

(1)

204

INVERTER ID NUMBER

1 00FF

0000

00FF (0

255) Note 1

1

205

COMMUNICATION
SELECTION

1 0007

0000:

OFF

(0)

0001: RS485

(1)

0002: Profibus, Modbus, DNet

(2)

0003: TOSLINE S-20

(3)

0004: 12 bit binary input

(4)

0005: 3-digit BCD (0.1Hz)

(5)

0006: 3-digit BCD (1Hz)

(6)

206 1

MASTER/SLAVE
SELECTION

1 0018

0000:

Slave

(0)

0008: Master (frequency command)

(1)

0010: Master (output frequency) (2)

207

RS485 BAUD RATE

1

0004

0000: Normal mode

(0)

0004: High-speed mode

(1)

208 2

TOSLINE-F10
COMMAND INPUT

1 0003

0000:

OFF

(0)

0001: Frequency command

(1)

0002: Command input

(2)

0003: Both (1) and (2)

(3)

209

TOSLINE-F10
MONITOR OUTPUT

1 003C

0000:

(0) 0020:

(8)

0004: (1)

0024: (9)

0008: (2)

0028: (10)

000C: (3)

002C: (11)

0010: (4)

0030: (12)

0014: (5)

0034: (13)

0018: (6)

0038: (14)

001C: (7)

003C: (15

)

20A

TOSLINE-F10 COMM
ERROR MODE

1

0080

0000: Data cleared

(0)

0080: Data retained

(1)

20B 3

TOSLINE-S20
RECEIVE ADDRESS

1 FFFF

0000

03FF (0

1023)

1

20C

TOSLINE-S20
TRANSMIT ADDRESS

1 FFFF

0000

03FF (0

1023)

1

20D

TOSLINE-S20
COMMAND INPUT

1 001F

0000

001F (0

31)

1

20E

TOSLINE-S20
MONITOR OUTPUT

1 001F

0000

001F (0

31)

1

20F

TOSLINE-S20 FREQ
REF ADDR SELECT

1 0001

0000:

Disable

(0)

0001: Enable

(1)

1

210

1

TOSLINE-S20
FREQ REFERENCE
ADDR

1 FFFF

0000

03FF (0

1023)

1

Note 1: Although the

INVERTER ID NUMBER

parameter can be set from 0 to 255, the allowable Profibus slave

addresses range only from 0 to 125. Therefore, if this parameter is set to a value from 126 to 255, the
Profibus interface card will trip “OPTION PCB ERROR” upon initialization.