beautypg.com

Group:fundamental parameters #2, Group:panel control parameters – Toshiba G3 TOSVERT-130 User Manual

Page 35

background image

34

11.2.2

11.2.2

11.2.2

11.2.2 GROUP:FUNDAMENTAL PARAMETERS #2

GROUP:FUNDAMENTAL PARAMETERS #2

GROUP:FUNDAMENTAL PARAMETERS #2

GROUP:FUNDAMENTAL PARAMETERS #2

Register

Function / Title

Bank

Mask

Adjustment Range

Multiplier

34

BASE FREQUENCY #2

0 / 1

FFFF

09C4

9C40 (25.00

400.00)

0.01

35

MAXIMUM OUTPUT
VOLTAGE #2

0 / 1

FFFF

0000

0258 (0

600)

1

36

VOLTAGE BOOST #2

0 / 1

FFFF

0000

012C (0.0

30.0)

0.1

37

ELECTRONIC THERMAL
PROTECT LVL #2

0 / 1

00FF

000A

0064 (10

100)

1

38

STALL PROTECTION
SELECTION #2

0 / 1

0040

0000: ON

(0)

0040: OFF

(1)

39 0

STALL PROTECTION
LEVEL #2

0 / 1

00FF

000A

00D7 (10

215)

1

3A

ACCELERATION TIME #2

0 / 1

FFFF

0001

EA60 (0.1~ 6000.0)

0001

EA60 (0.01~ 600.00)

0.1

0.01

3B

DECELERATION TIME #2

0 / 1

FFFF

0001

EA60 (0.1~ 6000.0)

0001

EA60 (0.01~ 600.00)

0.1

0.01

3C

ACC/DEC PATTERN #2
SELECTION

0 / 1

0030

0000: Linear

(0)

0010: Self-adjusting

(1)

0020: S-Pattern #1

(2)

0030: S-Pattern #2

(3)

3D

ACC/DEC #1/#2 SWITCH
FREQUENCY

0 / 1

FFFF

0000

Fmax

0.01




11.2.3

11.2.3

11.2.3

11.2.3 GROUP:PANEL CONTROL PARAMETERS

GROUP:PANEL CONTROL PARAMETERS

GROUP:PANEL CONTROL PARAMETERS

GROUP:PANEL CONTROL PARAMETERS

Register

Function / Title

Bank

Mask

Adjustment Range

Multiplier

3E

DIRECTION SELECTION
(FORWARD/REV)

0 / 1

0004

0000: Reverse

(0)

0004: Forward

(1)

3F

STOP PATTERN
SELECTION

0 / 1

0040

0000: Decelerated stop

(0)

0040: Coast stop

(1)

40

FUNDAMENTAL PARAM
SWITCHING

0 / 1

0004

0000: V/F #1

(1)

0004: V/F #2

(2)

41

ACCEL/DECEL #1/#2
SELECTION

0 / 1

0008

0000: Acc / dec #1

(1)

0008: Acc / dec #2

(2)

42

PANEL RESET SELECTION

0 / 1

0030

0000: All possible

(0)

0010: OL only

(1)

0020: OL, OC only

(2)

43

PANEL FEEDBACK
CONTROL

0 / 1

0001

0000: Feedback valid

(0)

0001: Feedback invalid

(1)