Group:special control parameters – Toshiba G3 TOSVERT-130 User Manual
Page 40
39
11.2.5
11.2.5
11.2.5
11.2.5 GROUP:SPECIAL CONTROL PARAMETERS
GROUP:SPECIAL CONTROL PARAMETERS
GROUP:SPECIAL CONTROL PARAMETERS
GROUP:SPECIAL CONTROL PARAMETERS
Register
Function / Title
Bank
Mask
Adjustment Range
Multiplier
69
START-UP FREQUENCY
0 / 1
FFFF
0000
∼
03E8 (0.00
∼
10.00)
0.01
6A
∼
6F
Reserved
70
END FREQUENCY
0 / 1
FFFF
0000
∼
0BB8 (0.00
∼
30.00)
0.01
71
RUN FREQUENCY
0 / 1
FFFF
0000
∼
Fmax
0.01
72
RUN FREQUENCY
HYSTERESIS
0 / 1
FFFF
0000
∼
0BB8 (0.00
∼
30.00)
0.01
73
ENABLE JUMP
FREQUENCIES
0 / 1
0080
0000: Function OFF
(0)
0080: Function ON
(1)
74 1
JUMP FREQUENCY #1
0 / 1
FFFF
0000
∼
Fmax
0.01
75
JUMP FREQUENCY #1
BANDWIDTH
0 / 1
FFFF
0000
∼
0BB8 (0.00
∼
30.00)
0.01
76
JUMP FREQUENCY #2
0 / 1
FFFF
0000
∼
Fmax
0.01
77
JUMP FREQUENCY #2
BANDWIDTH
0 / 1
FFFF
0000
∼
0BB8 (0.00
∼
30.00)
0.01
78
JUMP FREQUENCY #3
0 / 1
FFFF
0000
∼
Fmax
0.01
79
JUMP FREQUENCY #3
BANDWIDTH
0 / 1
FFFF
0000
∼
0BB8 (0.00
∼
30.00)
0.01
7A
∼
7F
Reserved
80
PWM CARRIER FREQUENCY
(Note
1)
0 / 1
00FF
0005
∼
0064 (0.5
∼
10.0)
0.1
Note 1: Actual adjustment range depends on inverter rating.