beautypg.com

Group:special control parameters – Toshiba G3 TOSVERT-130 User Manual

Page 40

background image

39

11.2.5

11.2.5

11.2.5

11.2.5 GROUP:SPECIAL CONTROL PARAMETERS

GROUP:SPECIAL CONTROL PARAMETERS

GROUP:SPECIAL CONTROL PARAMETERS

GROUP:SPECIAL CONTROL PARAMETERS

Register

Function / Title

Bank

Mask

Adjustment Range

Multiplier

69

START-UP FREQUENCY

0 / 1

FFFF

0000

03E8 (0.00

10.00)

0.01

6A

6F

Reserved

70

END FREQUENCY

0 / 1

FFFF

0000

0BB8 (0.00

30.00)

0.01

71

RUN FREQUENCY

0 / 1

FFFF

0000

Fmax

0.01

72

RUN FREQUENCY
HYSTERESIS

0 / 1

FFFF

0000

0BB8 (0.00

30.00)

0.01

73

ENABLE JUMP
FREQUENCIES

0 / 1

0080

0000: Function OFF

(0)

0080: Function ON

(1)

74 1

JUMP FREQUENCY #1

0 / 1

FFFF

0000

Fmax

0.01

75

JUMP FREQUENCY #1
BANDWIDTH

0 / 1

FFFF

0000

0BB8 (0.00

30.00)

0.01

76

JUMP FREQUENCY #2

0 / 1

FFFF

0000

Fmax

0.01

77

JUMP FREQUENCY #2
BANDWIDTH

0 / 1

FFFF

0000

0BB8 (0.00

30.00)

0.01

78

JUMP FREQUENCY #3

0 / 1

FFFF

0000

Fmax

0.01

79

JUMP FREQUENCY #3
BANDWIDTH

0 / 1

FFFF

0000

0BB8 (0.00

30.00)

0.01

7A

7F

Reserved

80

PWM CARRIER FREQUENCY

(Note

1)

0 / 1

00FF

0005

0064 (0.5

10.0)

0.1


Note 1: Actual adjustment range depends on inverter rating.