beautypg.com

Toshiba G3 TOSVERT-130 User Manual

Page 22

background image

21

Table 1 : Command Word Format

Bit Function

Setting

0

RUN command

0: Stop
1: Run

1

STOP Command (has priority
over RUN command)

0: run enabled
1: stop

2

Forward / reverse run
selection

0: reverse
1: forward

3

Acc/dec #1 / #2 selection

0: Acc / dec #1
1: Acc / dec #2

4 Reserved

5 Reserved

6 Reserved

Value is ignored

Low Byt

e

7

Jog mode selection

0: Normal (acc/dec mode)
1: Jog mode

8

Feedback control

0: Feedback valid
1: Feedback invalid

9

Compulsory DC injection
braking mode

0: No compulsory DC injection braking
1: Compulsory DC injection below

DC

INJECTION START FREQUENCY

A Fundamental

parameter

switching

0: V/F #1
1: V/F #2

B

Gate block (coast stop)
command

0: Normal
1: Gate block

C

Emergency off command

0: Does nothing
1: Emergency off

D

Reset command (trip clear)

0: Does nothing
1: Reset when tripped

E Reserved

High Byt

e

F Reserved

Value is ignored