37 table 7: input terminal selections – Toshiba G3 TOSVERT-130 User Manual
Page 38
37
Table 7: Input Terminal Selections
Setting
Value
Data
(Hex)
Function Setting
Value
Data
(Hex)
Function
0
10C8
R
(reverse run)
28
04AF
Binary bit #6
1
011C
SS1 (preset speed selection)
29
08AF
Binary bit #7
2
021C
SS2 (preset speed selection)
30
10AF
Binary bit #8
3
041C
SS3 (preset speed selection)
31
20AF
Binary bit #9
4
081C
SS4 (preset speed selection)
32
40AF
Binary bit #10
5 20C8
F
(forward
run)
33 04CE
No
effect
6
201B
RES (fault reset)
34
01C7
UP/DOWN frequency setting (UP)
7
C0C9
ST
(gate ON/OFF)
35
02C7
UP/DOWN frequency setting
(DOWN)
8
0CC8
JOG selection
36
04C7
UP/DOWN frequency clear
9
081A
Acc/dec #1/#2 selection
37
08C7
PUSH-type RUN key
10
101B
Emergency off
38
10C7
PUSH-type STOP key
11
021B
DC injection braking ON/OFF
39
02B9
No effect
12 041B
Fundamental
parameter
switching (V/F #2)
40
C0C8
Forward/reverse run selection
13
011B
Feedback control ON/OFF
41
20C7
RUN
14
10CE
Pattern run selection #1
42
30C9
Binary data write
15
20CE
Pattern run selection #2
43
0198
[LOCAL/REMOTE] key
16
40CE
Pattern run selection #3
44
0298
[MON] key
17
80CE
Pattern run selection #4
45
0498
[PRG] key
18
02CE
Pattern run continue signal
46
0898
[UP] (▲) key
19
01CE
Pattern run step trigger signal
47
1098
[DOWN] (▼) key
20
0AC9
JOG forward run
48
2098
[READ/WRITE] key
21
06C9
JOG reverse run
49
4098
[RUN] key
22
10AE
Binary bit #0
50
8098
[STOP/CLEAR] key
23
20AE
Binary bit #1
51
08CE
Commercial power / inverter
switching signal
24
40AE
Binary bit #2
52
40C7
Reserved for option use
25
80AE
Binary bit #3
53
10CB
RR frequency switching input
26
01AF
Binary bit #4
54
20CB
IV frequency switching input
27
02AF
Binary bit #5
Note: In order for binary bit #0
∼
#10 (setting values 22
∼
32) and UP/DOWN frequency setting (setting values 34 &
35) inputs to be valid, parameter
FREQUENCY PRIORITY SELECTION #1
or
FREQUENCY PRIORITY
SELECTION #2
in
GROUP:FREQUENCY SETTING PARAMETERS
must be set to 5 (BIN (binary setting or
UP/DOWN setting)).