beautypg.com

G3 parameter settings – Toshiba G3 TOSVERT-130 User Manual

Page 18

background image

17

7.

7.

7.

7. G3 Parameter Settings

G3 Parameter Settings

G3 Parameter Settings

G3 Parameter Settings

Profibus interface board communications are enabled by setting parameter

COMMUNICATION SELECTION

in

GROUP:COMMUNICATION SETTING PARAMETERS

to 2 (Profibus, Modbus, DeviceNet). None of the Tosline-F10 communication
parameter settings apply when using the Profibus interface. For more information on
methods for changing parameter settings, refer to the TOSHIBA G3 Operation
Manual.

The following is a list of the parameter settings that are required during setup to
enable Profibus communications:

Parameter Group

Required

Value

BLIND FUNCTION
SELECTION

GROUP:UTILITY
PARAMETERS

1

COMMUNICATIONS PARMS
BLIND

GROUP:UTILITY
PARAMETERS

1

COMMUNICATION
SELECTION

GROUP:COMMUNICATION
SETTING PARAMETERS

2

INVERTER ID NUMBER

GROUP:COMMUNICATION
SETTING PARAMETERS

any value other than

126

255.


Note: Although

the

INVERTER ID NUMBER

parameter can be set from 0 to 255,

the allowable Profibus slave addresses range only from 0 to 125. Therefore,
if this parameter is set to a value from 126 to 255, the Profibus interface card
will trip “

OPTION PCB ERROR

” upon initialization. To correct this error, set

the

INVERTER ID NUMBER

parameter to a value from 0 to 125.


To implement any parameter changes in

GROUP:COMMUNICATION SETTING

PARAMETERS

, the drive must be reset after making the changes.


If the drive into which a Profibus communications interface board is installed trips

OPTION PCB ERROR

” for any reason during initialization or operation (for example,

if it becomes loose from its mounting connections), it is incapable of being reset via
the Profibus network. When this trip condition occurs, therefore, the drive can only
be reset locally via the panel or control terminal block.

If drive control (frequency command input, RUN/STOP, etc.) is to be performed via
the Profibus network, the following inverter parameters must also be set as shown:

Parameter Group

Required

Value

COMMAND MODE SELECTION

GROUP:UTILITY PARAMETERS

3

FREQUENCY MODE SELECTION

GROUP:UTILITY PARAMETERS

3


Of course, input data can always be monitored from the network regardless of the
settings of

COMMAND MODE SELECTION

and

FREQUENCY MODE SELECTION

. Also

note that if the

COMMAND MODE SELECTION

or

FREQUENCY MODE SELECTION

parameters are changed while the drive is running, the change will not take effect
until the next time the drive is stopped.