Register
Function / Title
Bank
Mask
Adjustment Range
Multiplier
190
FEEDBACK CONTROL
SELECTION
0 / 1
0060
0020: No feedback
(0)
0040: PID control
(1)
0060: Speed feedback
(2)
191 1,
2
FEEDBACK INPUT
SIGNAL SELECTION
0 / 1
001C
0004: RR input
(1)
0008: IV input
(2)
000C: RX input
(3)
0010: PG feedback
(4)
0014: RS232C input
(5)
0018: Communication/12-bit binary
interface board
(6)
001C: BIN input
(7)
192
PROPORTIONAL
GAIN
0 / 1
00FF
0001
∼
00FF (0.01
∼
2.55)
0.01
193
INTEGRAL GAIN
0 / 1
FFFF
0001
∼
8CA0 (0.01
∼
360.00)
0.01
194
ANTI-HUNTING
GAIN
0 / 1
00FF
0000
∼
00FF (0.0
∼
25.5)
0.1
195
LAG TIME
CONSTANT
0 / 1
00FF
0000
∼
00FF (0
∼
255)
1
196
PID LOWER LIMIT
FREQUENCY
0 / 1
FFFF
0
∼
Fmax
0.01
197
PID DEVIATION LIMIT
SELECTION
0 / 1
0080
0000: No PID deviation limit
(0)
0080: PID deviation limited
(1)
198 1
PID DEVIATION
UPPER LIMIT
0 / 1
00FF
0000
∼
0032 (0
∼
50)
1
199
PID DEVIATION
LOWER LIMIT
0 / 1
00FF
0000
∼
0032 (0
∼
50)
1
19A
PG INPUT: NUMBER OF
PULSES
0 / 1
FFFF
0001
∼
270F (1
∼
9999)
1
19B
PG INPUT: NUMBER OF
PHASES
0 / 1
0001
0000: Single-phase input
(1)
0001: Two-phase input
(2)
19C
DROOPING CONTROL
ENABLE
0 / 1
0002
0000: OFF
(0)
0002: ON
(1)
19D 1
DROOPING CONTROL
AMOUNT
0 / 1
00FF
0000
∼
0064 (0
∼
10.0)
0.1
19E
OVERRIDE CONTROL
SELECTION
0 / 1
0007
0000: OFF
(0)
0001: FCRR
(1)
0002: FCIV
(2)
0003: FCRX
(3)
0004: FCPG
(4)
0005: FCPNL
(5)
0006: FCOPT
(6)
0007: FCMLT
(7)
19F 7
OVERRIDE
MULTIPLIER INPUT
SELECTION
0 / 1
0038
0000: Reference
(0)
0008: KRR
(1)
0010: KIV
(2)
0018: KRX
(3)
0020: KBIN
(4)
1A0
OVERRIDE CHANGE
MULTIPLIER
0 / 1
FFFF
FC18
∼
03E8 (-100.0
∼
100.0)
0.1
1A1
∼
1CF
Reserved